Monitor display and monitor output signal
4.11 Monitor display and monitor output signal
4.11.1 Speed display and speed setting (Pr. 37)
The above parameter can be set when
Pr. 160 Extended function display selection
= "0".
* The maximum value of the setting range differs according to the
Pr. 1 Maximum frequency (Pr. 18 High speed maximum frequency)
,
and it can be calculated from the
following formula.
Note that the maximum setting value of
Pr. 37
is 9998 if the result of the above formula exceeds 9998.
To display the machine speed, set in
Pr. 37
the machine speed for 60Hz operation.
For example, when
Pr. 37
= "1000", "1000" is displayed on the output frequency and set frequency monitor when the
running frequency is 60Hz. When running frequency is 30Hz, "500" is displayed.
Each monitored item has the following setting increments.
∗1
Machine speed conversion formula ..........
Pr. 37
×
frequency/60Hz
Purpose
Parameter that should be Set
Refer to
Page
Display motor speed
Set speed
Speed display and speed setting
Pr. 37
Change PU monitor display data
Monitor display/PU main display
data selection
Cumulative monitor clear
Pr. 52, Pr. 54, Pr. 170, Pr. 171,
Pr. 268, Pr. 563, Pr. 564, Pr. 891
Change the monitor output from
terminal FM
Terminal FM function selection
Pr. 54
Set the reference of the monitor
output from terminal FM
Terminal FM standard setting
Pr. 55, Pr. 56
Adjust terminal FM outputs
Terminal FM calibration
Pr. 900
The monitor display and frequency setting of the PU (FR-PU04/FR-PU07) can be changed to the machine speed.
Parameter
Number
Name
Initial
Value
Setting Range
Description
37
Speed display
0
0
Frequency display, setting
0.01 to 9998
∗
Machine speed at 60Hz.
Maximum setting value of
Pr. 37
<
16777.215
×
60 (Hz)
Setting value of
Pr. 1 (Pr. 18)
(Hz)
Pr. 37
Setting
Output Frequency
Monitor
Set Frequency Monitor
Frequency Setting
Parameter Setting
0 (initial value)
0.01Hz
0.01Hz
0.01Hz
0.01Hz
0.01 to 9998
0.001 (Machine speed
)
0.001 (Machine speed
)
0.001 (Machine speed
NOTE
Under V/F control, the output frequency of the inverter is displayed in terms of synchronous speed, and therefore,
displayed value = actual speed + motor slip. The display changes to the actual speed (estimated value calculated
based on the motor slip) when slip compensation was valid.
Refer to
Pr. 52
when you want to change the PU main monitor (PU main display).
Since the panel display of the operation panel is 4 digits in length, the monitor value of more than "9999" is displayed as "----".
When the machine speed is displayed on the FR-PU04/FR-PU07, do not change the speed by using an up/down key in
the state where the set speed exceeding 65535 is displayed. The set speed may become arbitrary value.
While the machine speed is displayed on the monitor, values of other parameters related to speed (
Pr. 1
, etc.) are in
frequency increments. Set other parameters (
Pr.1
, etc.) related to speed in increments of frequency.
Due to the limitations on the resolution of the set frequency, the indication in the second decimal place may differ
from the setting.
CAUTION
Make sure that the running speed setting is correct.
Otherwise, the motor might run at extremely high speed, damaging the machine.
Parameters referred to
Pr. 1 Maximum frequency, Pr. 18 High speed maximum frequency
Pr. 52 DU/PU main display data selection
Содержание FR-D710W-0.1K
Страница 45: ...36 MEMO ...
Страница 61: ...52 MEMO ...
Страница 254: ...252 MEMO ...
Страница 296: ...294 MEMO ...
Страница 297: ...295 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Страница 312: ...4 4 BCN C22005 689 MEMO ...