Function assignment of external terminal and control
(2) Zero current detection (Y13 signal,
Pr. 152, Pr. 153
)
If the output current remains lower than the
Pr. 152
setting
during inverter operation for longer than the time set in
Pr.
153
, the zero current detection (Y13) signal is output from the
inverter's open collector or relay output terminal.
When the inverter's output current falls to "0", torque will not
be generated. This may cause a drop due to gravity when
the inverter is used in vertical lift application.
To prevent this, the Y13 signal can be output from the
inverter to close the mechanical brake when the output
current has fallen to "zero".
For the Y13 signal, set "13 (positive logic) or 113 (negative
logic)" in
Pr.190, Pr.192 or Pr.197 (output terminal function
selection)
and assign functions to the output terminal.
REMARKS
This function is also valid during execution of the offline auto tuning.
The response time of Y12 and Y13 signals is approximately 0.1s. Note that the response time changes according to the load
condition.
When
Pr. 152
= "0", detection is disabled.
NOTE
Changing the terminal assignment using
Pr. 190, Pr. 192, and Pr. 197 (output terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
CAUTION
The zero current detection level setting should not be too low, and the zero current detection time setting not
too long. Otherwise, the detection signal may not be output when torque is not generated at a low output
current.
To prevent the machine and equipment from resulting in hazardous conditions detection signal, install a
safety backup such as an emergency brake even the zero current detection function is set valid.
Parameters referred to
Offline auto tuning
Pr. 190, Pr. 192, Pr. 197 (output terminal function selection)
OFF
ON
Start signal
Time
Output current
OFF
ON
Zero current
detection time
(Y13)
Pr. 153
Detection time
Pr. 153
Detection time
Pr. 152
OFF
ON
0[A]
0.1s*
Pr. 152
* The zero current detection signal (Y13) holds the
signal for approximately 0.1s once turned ON.
Содержание FR-D710W-0.1K
Страница 45: ...36 MEMO ...
Страница 61: ...52 MEMO ...
Страница 254: ...252 MEMO ...
Страница 296: ...294 MEMO ...
Страница 297: ...295 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Страница 312: ...4 4 BCN C22005 689 MEMO ...