173
Selection of operation mode and operation location
(4) Selection of control source in network operation mode
(Pr. 338, Pr. 339)
As control sources, there are the operation command source that controls the signals related to the inverter start
command and function selection and the speed command source that controls the signals related to frequency setting.
In network operation mode, the commands from the external terminals and communication are as listed below.
[Explanation of table]
External
: Command is valid only from control terminal.
NET
: Command only from communication is valid
Combined : Command from both control terminal and communication is valid.
—
: Command from either of control terminal and communication is invalid.
Operation
Location
Selection
Pr. 338 Communication operation
command source
0: NET
1: External
Remarks
Pr. 339 Communication speed
command source
0: NET
1: External 2: External 0: NET
1: External 2: External
Fixed
function
(terminal-
equivalent
function)
Running frequency from
communication
NET
—
NET
NET
—
NET
Terminal 2
—
External
—
—
External
—
Terminal 4
—
External
—
External
Sel
ecti
ve func
ti
on
Pr
. 178
to Pr
. 182
settin
g
0
RL
Low speed operation
command/remote setting
clear
NET
External
NET
External
Pr. 59
=
"0"
(multi-speed)
Pr. 59
≠
"0"
(remote)
1
RM
Middle speed operation
command/remote setting
function
NET
External
NET
External
2
RH
High speed operation
command/remote setting
function
NET
External
NET
External
3
RT Second function selection
NET
External
4
AU Current input selection
—
Combined
—
Combined
5
JOG Jog operation selection
—
External
7
OH External thermal relay input
External
8
REX Fifteen speed selection
NET
External
NET
External
Pr. 59 =
"0"
(multi-speed)
10
X10
Inverter operation enable
signal
External
12
X12
PU operation external
interlock
External
14
X14 PID control valid terminal
NET
External
NET
External
16
X16
PU-external operation
switchover
External
18
X18 V/F switching
NET
External
24 MRS
Output stop
Combined
External
Pr. 79
≠
"7"
PU operation interlock
External
Pr. 79 =
"7"
When the X12
signal is not
assigned
25 STOP Start self-holding selection
—
External
37
X37 Traverse function selection
NET
External
60 STF Forward rotation command
NET
External
61 STR Reverse rotation command
NET
External
62 RES Reset
External
65
X65
PU/NET operation
switchover
External
66
X66
NET-external operation
switching
External
67
X67
Command source
switchover
External
REMARKS
The command source of communication is as set in
Pr. 551
.
The
Pr. 338
and
Pr. 339
settings can be changed while the inverter is running when
Pr. 77
= "2". Note that the setting change is
reflected after the inverter has stopped. Until the inverter has stopped, communication operation command source and
communication speed command source before the setting change are valid.