14
Wiring
2.1 Wiring
2.1.1
Terminal connection diagram
NOTE
To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the power cables.
After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes
in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
To ensure safety, for single-phase power input specification model, connect the power input to the inverter via a
magnetic contactor and earth leakage circuit breaker or moulded case circuit breaker, and use the magnetic
contactor to switch power on-off.
The output of the single-phase power input specification is three-phase 200V.
Earth
(Ground)
Motor
IM
Earth (Ground)
Three-phase
AC power
supply
MCCB
MC
R/L1
P1
+
PR
-
S/L2
T/L3
U
V
W
Earth
(Ground)
Forward
rotation start
Reverse
rotation start
Middle
speed
High
speed
Low
speed
Control input signals (No voltage input allowed)
Contact input common
24VDC power supply
Contact input common
(Common for external power supply transistor)
STR
STF
RH
RM
RL
SD
PC
Relay output
Running
Open collector output
Open collector output common
Sink/source common
RUN
SE
A
B
C
AM
5
Frequency setting signals (Analog)
2 0 to 5VDC
10(+5V)
2
3
1
4 4 to 20mADC
Frequency
setting
potentiometer
1/2W1k
Ω
Terminal 4
input
(Current
input)
(+)
(-)
5(Analog common)
*5 It is recommended to use 2W1k
Ω
when the frequency setting signal
is changed frequently.
*5
*3 Terminal input specifications
can be changed by analog
input specifications
switchover (
Pr. 73
).
*2 When using terminals PC-
SD as a 24VDC power
supply, take care not to
short across terminals
PC-SD.
PU
connector
Control circuit terminal
Main circuit terminal
Source logic
Jumper
*1
*7
*2
*3
*4
Terminal functions vary
with the input terminal
assignment (
Pr. 178 to
Pr. 182
)
Multi-speed selection
Terminal functions vary by
Pr. 190
RUN terminal function selection
Terminal functions vary
by
Pr. 192
A,B,C terminal
function selection
SINK
SOURCE
V
I
*4
0 to 5VDC
(0 to 10VDC)
0 to 10VDC
*4 Terminal input
specifications can be
changed by analog input
specifications switchover
(
Pr. 267
). Set the
voltage/current input
switch in the "
V
" position
to select voltage input (0
to 5V/0 to10V) and "
I
"
(initial value) to select
current input (4 to 20mA).
Voltage/current
input switch
Main circuit
Control circuit
R
Relay output
(Fault output)
Brake unit
(Option)
(+)
(-)
Analog signal output
(0 to 10VDC)
*6
24V
Inrush current
limit circuit
*
1. DC reactor (FR-HEL)
When connecting a DC reactor, remove the
jumper across P1-
+
Single-phase
AC power
supply
MCCB
MC
L1
N
Single-phase power input
*6 A brake transistor is not built-in to the
FR-D720S-008 and 014.
*7 Brake resistor (FR-ABR, MRS)
Install a thermal relay to prevent an
overheat and burnout of the brake resistor.
(The brake resistor can not be connected
to the FR-D720S-008 and 014.)