![Mitsubishi Electric FR-D700 Series Скачать руководство пользователя страница 75](http://html.mh-extra.com/html/mitsubishi-electric/fr-d700-series/fr-d700-series_instruction-manual_239211075.webp)
71
Adjust the output torque (current) of the motor
(2) Selection method of general-purpose magnetic flux vector control
Perform secure wiring.
Display the extended function parameters.
(Pr. 160) (Refer to page 157)
Set "0" in
Pr. 160
to display the extended function parameters.
Set the motor.
(Pr. 71)
Motor
Pr. 71
Setting
Remarks
Mitsubishi standard
motor
Mitsubishi high
efficiency motor
SF-JR
0 (initial value)
SF-HR
40
Others
3
Offline auto tuning is necessary.
Mitsubishi constant-
torque motor
SF-JRCA 4P
1
SF-HRCA
50
Others (SF-JRC, etc.)
13
Offline auto tuning is necessary.
Other standard motor
—
3
Offline auto tuning is necessary.
Other constant-
torque motor
—
13
Offline auto tuning is necessary.
∗1
, for other settings of
Pr. 71
.
∗2
Set the motor capacity.
(Pr. 80) (Refer to page 74)
Set motor capacity (kW) in
Pr. 80 Motor capacity.
(V/F control is performed when the setting is "9999" (initial value).
Set the operation command.
Select the start command and speed command.
(1)Start command
1)Operation panel: Setting by pressing
of the operation panel
2)External command: Setting by forward rotation or reverse rotation
command (terminal STF or STR)
(2)Speed command
1)Operation panel: Setting by pressing
of the operation panel
2)External analog command (terminal 2 or 4):
Give a speed command using the analog signal input to terminal 2 (or
terminal 4).
3)Multi-speed command:
The external signals (RH, RM, RL) may also be used to give speed
command.
Test run
As required
Perform offline auto tuning.
(Pr. 96) (Refer to page 100)
Set slip compensation.
(Pr. 245, Pr. 246, Pr. 247) (Refer to page 73)
NOTE
Uneven rotation slightly increases as compared to the V/F control. (It is not suitable for machines such as grinding
machine and wrapping machine which requires less uneven rotation at low speed.
When a surge voltage suppression filter (FR-ASF-H/FR-BMF-H) is connected between the inverter and motor, output
torque may decrease.)