Function assignment of external terminal and control
4.10.6 Detection of output frequency (SU, FU signal, Pr. 41 to Pr. 43)
The inverter output frequency is detected and output at the output signals.
Parameter
Number
Name
Initial Value
Setting Range
Description
41
Up-to-frequency
sensitivity
10%
0 to 100%
Level where the SU signal turns on.
42
Output frequency
detection
6Hz
0 to 400Hz
Frequency where the FU signal turns on.
43
Output frequency
detection for reverse
rotation
9999
0 to 400Hz
Frequency where the FU signal turns on in reverse
rotation.
9999
Same as
Pr. 42
setting
The above parameters can be set when
Pr. 160 Extended function display selection
= "0".
(1) Up-to-frequency sensitivity (SU signal,
Pr. 41
)
When the output frequency reaches the set frequency, the
up-to-frequency signal (SU) is output.
The
Pr. 41
value can be adjusted within the range 0% to
±
100% on the assumption that the set frequency is 100%.
This parameter can be used to ensure that the running
frequency has been reached to provide the operation start
signal etc. for related equipment.
When using the SU signal, set "1 (positive logic) or 101
(negative logic)" in
Pr. 190 or Pr. 192 (output terminal function
selection)
to assign function to the output terminal.
(2) Output frequency detection
(FU signal,
Pr. 42, Pr. 43
)
The output frequency detection signal (FU) is output when
the output frequency reaches or exceeds the
Pr. 42
setting.
This function can be used for electromagnetic brake
operation, open signal, etc.
When the detection frequency is set to
Pr. 43
, frequency
detection for reverse operation use only can also be set.
This function is effective for switching the timing of
electromagnetic brake operation between forward rotation
(rise) and reverse rotation (fall) during vertical lift operation,
etc.
When
Pr. 43
≠
"9999", the
Pr. 42
setting is used for forward
rotation and the
Pr. 43
setting is used for reverse rotation.
When using the FU signal, set "4 (positive logic)" or "104
(negative logic)" to
Pr. 190 or Pr. 192 (output terminal function
selection)
to assign the function to the output terminal.
REMARKS
All signals are off during DC injection brake.
The output frequency to be compared with the set frequency is the output frequency before slip compensation is performed.
NOTE
Changing the terminal assignment using
Pr.190, Pr.192 (output terminal function selection)
may affect the other functions.
Make setting after confirming the function of each terminal.
Parameters referred to
Pr. 190, Pr. 192 (output terminal function selection)
Output frequency
(Hz)
ON
Set frequency
Adjustment
range
Pr.41
SU
Time
OFF
OFF
Output signal
Forward
rotation
Reverse
rotation
Time
Output frequency (Hz)
ON
ON
OFF
OFF
OFF
FU
Pr.43
Pr.42
Содержание FR-D700 Series
Страница 11: ...VII MEMO ...
Страница 23: ...12 MEMO ...
Страница 57: ...46 MEMO ...
Страница 262: ...258 MEMO ...
Страница 276: ...272 MEMO ...
Страница 283: ...279 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 287: ...283 MEMO ...
Страница 289: ......