192
Communication operation and setting
Example) When reading the
C3 (Pr. 902)
and
C6 (Pr. 904)
settings from the inverter of station 0
To read/write
C3 (Pr. 902)
and
C6
(Pr. 904)
after inverter reset or parameter clear, execute from 1) again.
List of calibration parameters
[Special monitor selection No.]
Refer to
for details of the monitor description.
∗1
When "0.01 to 9998" is set in
Pr. 37
and "01" in instruction code HFF, the data format is 6 digits (E2).
∗2
Input terminal monitor details
∗3
Output terminal monitor details
REMARKS
Set 65520 (HFFF0) as a parameter value "8888" and 65535 (HFFFF) as "9999".
For the instruction codes HFF, HEC and HF3, their values are held once written but cleared to zero when an inverter reset or all
clear is performed.
Computer Send Data
Inverter Send Data
Description
1)
ENQ 00 FF 0 01 82
ACK 00
Set "H01" to the expansion link parameter.
2)
ENQ 00 EC 0 01 7E
ACK 00
Set "H01" to second parameter changing.
3)
ENQ 00 5E 0 0F
STX 00 0000 ETX 25
C3 (Pr. 902)
is read. 0% is read.
4)
ENQ 00 60 0 FB
STX 00 0000 ETX 25
C6 (Pr. 904)
is read. 0% is read.
b15
b0
—
—
—
—
—
—
—
—
—
RH
RM
RL
—
—
STR
STF
b15
b0
—
—
—
—
—
—
—
—
—
—
ABC
—
—
—
—
RUN
Parameter
Name
Instruction
Code
Rea
d
Wr
ite
Ext
ended
C2 (902) Terminal 2 frequency setting bias frequency
5E DE
1
C3 (902) Terminal 2 frequency setting bias
5E DE
1
125 (903)
Terminal 2 frequency setting gain
frequency
5F DF
1
C4 (903) Terminal 2 frequency setting gain
5F DF
1
C5 (904) Terminal 4 frequency setting bias frequency
60
E0
1
C6 (904) Terminal 4 frequency setting bias
60
E0
1
126 (905)
Terminal 4 frequency setting gain
frequency
61
E1
1
C7 (905) Terminal 4 frequency setting gain
61
E1
1
Data
Description
Unit
H01
Output frequency/speed
∗1
0.01Hz/
0.001
H02
Output current
0.01A
H03
Output voltage
0.1V
H05
Frequency setting/speed setting
∗1
0.01Hz/
0.001
H08
Converter output voltage
0.1V
H09
Regenerative brake duty
0.1%
H0A
Electronic thermal relay function
load factor
0.1%
H0B
Output current peak value
0.01A
H0C
Converter output voltage peak value
0.1V
H0E
Output power
0.01kW
H0F
Input terminal status
∗2
—
H10
Output terminal status
—
H14
Cumulative energization time
1h
H17
Actual operation time
1h
H18
Motor load factor
0.1%
H19
Cumulative power
1kWh
H34
PID set point
0.1%
H35
PID measured value
0.1%
H36
PID deviation
0.1%
H3D
Motor thermal load factor
0.1%
H3E
Inverter thermal load factor
0.1%
H3F
Cumulative power 2
0.01kWh
H40
PTC thermistor resistance
0.01k
Ω
Data
Description
Unit