215
Special operation and frequency control
4.20.2 Dancer control (Pr. 44, Pr. 45, Pr. 128 to Pr. 134)
Performs PID control by feedbacking the position detection of the dancer roller, controlling the dancer roller is in the
specified position.
Parameter
Number
Name
Initial Value
Setting
Range
Description
44
Second
acceleration/
deceleration time
FR-D740-080 or less
FR-D720S-008 to 100
5s
0 to 3600s
This parameter is the acceleration time of the main
speed during dancer control. It will not function as
second acceleration/deceleration time.
FR-D740-120 and 160 10s
45
Second
deceleration time
9999
0 to 3600s
This parameter is the deceleration time of the main
speed during dancer control. It will not function as
second deceleration time.
9999
128
PID action
selection
0
0
PID action is not performed
20
PID reverse
action
Measured value (terminal 4)
Set value (terminal 2 or
Pr. 133
)
21
PID forward
action
40
PID reverse
action
Addition
method: fixed
For dancer control
set point
(Pr. 133)
,
measured value
(terminal 4)
main speed (speed
command of the
operation mode)
41
PID forward
action
Addition
method: fixed
42
PID reverse
action
Addition
method: ratio
43
PID forward
action
Addition
method: ratio
129
PID proportional
band
100%
0.1 to 1000%
If the proportional band is narrow (parameter
setting is small), the manipulated variable varies
greatly with a slight change of the measured value.
Hence, as the proportional band narrows, the
response sensitivity (gain) improves but the
stability deteriorates, e.g. hunting occurs. Gain Kp
= 1/proportional band
9999
No proportional control
130
PID integral time
1s
0.1 to 3600s
For deviation step input, time (Ti) required for only
the integral (I) action to provide the same
manipulated variable as that for the proportional (P)
action. As the integral time decreases, the set point
is reached earlier but hunting occurs more easily.
9999
No integral control.
131
PID upper limit
9999
0 to 100%
Maximum value
If the feedback value exceeds the setting, the FUP
signal is output. The maximum input (20mA/5V/
10V) of the measured value (terminal 4) is
equivalent to 100%.
9999
No function
132
PID lower limit
9999
0 to 100%
Minimum value
If the process value falls below the setting range,
the FDN signal is output. The maximum input
(20mA/5V/10V) of the measured value (terminal 4)
is equivalent to 100%.
9999
No function
133
PID action set
point
9999
0 to 100%
Used to set the set point for PID control.
9999
Always 50%
134
PID differential
time
9999
0.01 to 10.00s
For deviation ramp input, time (Td) required for
providing only the manipulated variable for the
proportional (P) action.
As the differential time increases, greater response
is made to a deviation change.
9999
No differential control.
The above parameters can be set when
Pr.160 Extended function display selection
="0".
∗1
Pr. 129, Pr. 130, Pr. 133 and Pr.134
can be set during operation. They can also be set independently of the operation mode.
Содержание FR-D700 Series
Страница 11: ...VII MEMO ...
Страница 23: ...12 MEMO ...
Страница 57: ...46 MEMO ...
Страница 262: ...258 MEMO ...
Страница 276: ...272 MEMO ...
Страница 283: ...279 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 287: ...283 MEMO ...
Страница 289: ......