106
Motor brake and stop operation
(3) When a high power factor converter (FR-HC) is used and automatic restart after instantaneous
power failure function is made valid.
When automatic restart after instantaneous power failure function of both the FR-HC and inverter is made valid (when a
value other than "9999" is set in
Pr. 57 Restart coasting time
), set "2" in
Pr. 30
.
Set
Pr. 70
to "0%" (initial value).
When the FR-HC detects power failure during inverter operation, the RDY signal turns on, resulting in the motor coasting.
Turning the RDY signal off after power restoration, the inverter detects the motor speed (depends on the
Pr.162 Automatic
restart after instantaneous power failure selection
) and restarts automatically after instantaneous power failure.
(4) Regenerative brake duty alarm output and alarm signal (RBP signal)
100%: regenerative overvoltage protection operation value
[RB] appears on the operation panel and an alarm
signal (RBP) is output when 85% of the regenerative
brake duty set in
Pr. 70
is reached.
If the regenerative
brake duty reaches 100% of the
Pr. 70
setting, a
regenerative overvoltage (E.OV1 to E.OV3) occurs.
Note that [RB] is not displayed when
Pr. 30
= "0".
The inverter does not trip even when the alarm (RBP)
signal is output.
For the terminal used for the RBP signal output, assign
the function by setting "7 (positive logic) or 107
(negative logic)" in
Pr. 190 or Pr. 192 (output terminal
function selection)
.
REMARKS
The MRS signal can also be used instead of the X10 signal.
Refer to
to
for connecting the brake resistor (MRS type), high-duty brake resistor (FR-ABR), brake unit (FR-BU2),
high power factor converter (FR-HC), and power regeneration common converter (FR-CV).
NOTE
When terminal assignment is changed using
Pr. 178 to Pr. 182 (input terminal function selection) and Pr. 190, Pr. 192 (output
terminal function selection)
, the other functions may be affected. Make setting after confirming the function of each
terminal.
WARNING
The value set in
Pr. 70
must not exceed the setting of the brake resistor used.
Otherwise, the resistor can overheat.
Parameters referred to
Pr. 57 Restart coasting time
Pr. 178 to Pr. 182 (input terminal function selection)
Pr. 190, Pr. 192 (output terminal function selection)
Regenerative brake
pre-alarm (RBP)
Time
ON
ON
OFF
100
85
Ratio of the brake
duty to the
Pr. 70
setting (%)