121
Function assignment of external terminal and control
4.10.8 Remote output selection (REM signal, Pr. 495, Pr. 496)
You can utilize the on/off of the inverter's output signals instead of the remote output terminal of the programmable logic
controller.
Parameter
Number
Name
Initial
Value
Setting
Range
Description
495
Remote output
selection
0
0
Remote output data clear at powering off
Remote output data
clear at inverter reset
1
Remote output data retention at
powering off
10
Remote output data clear at powering off Remote output data
retention at inverter
reset
11
Remote output data retention at
powering off
496*
Remote output data 1
0
0 to 4095
Refer to the following diagram.
The above parameters can be set when
Pr. 160 Extended function display selection
= "0".
* The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in
Pr. 77 Parameter write selection
.
<
Remote output data
>
Pr. 496
The output terminal can be turned on/off depending on
the
Pr. 496
setting. The remote output selection can be
controlled on/off by computer link communication from
the PU connector.
Set "96 (positive logic) or 196 (negative logic)" to
Pr. 190
or Pr. 192 (output terminal function selection)
, and assign the
remote output (REM) signal to the terminal used for
remote output,
When you refer to the diagram on the left and set 1 to the
terminal bit (terminal where the REM signal has been
assigned) of
Pr. 496
, the output terminal turns on (off for
negative logic). By setting 0, the output terminal turns off
(on for negative logic).
b11
b0
∗
∗
∗
∗
∗
∗
AB
C
∗
∗
∗
∗
RU
N
∗
Any
Example: When "96 (positive logic)" is set in
Pr. 190 RUN terminal function selection
and "1" (H01) is set in
Pr. 496
, the
terminal RUN turns on.
ON/OFF example for positive logic
When
Pr. 495
= "0 (initial value), 10", performing a power on
reset (including a power failure) clears the REM signal
output. (The ON/OFF status of the terminals are as set in
Pr.
190, Pr. 192
. ) The
Pr. 496
setting is also "0".
When
Pr. 495
= "1, 11", the remote output data before power
off is stored into the EEPROM, so the signal output at power
recovery is the same as before power off. However, it is not
stored when the inverter is reset (terminal reset, reset
request through communication).
(See the chart on the left)
When
Pr. 495
= "10, 11", signal before rest is saved even at
inverter reset.
REMARKS
The output terminal where the REM signal is not assigned using
Pr. 190 or Pr. 192
does not turn on/off if 0/1 is set to the terminal
bit of
Pr. 496 or Pr. 497
. (It turns on/off with the assigned function.)
When the inverter is reset (terminal reset, reset request through communication),
Pr. 496
values turn to "0". When
Pr. 495
= "1,
11", however, they are the settings at power off. (The settings are stored at power off.)
When
Pr. 495
="10, 11", they are the same as before an inverter reset is made.
Parameters referred to
Pr. 190, Pr. 192 (output terminal function selection)
Power
supply
OFF
OFF
ON
OFF
REM
REM
REM signal clear
REM signal held
Inverter
reset time
(about 1s)
Pr. 495
= 0, 10
Pr. 495
= 1, 11
Power
supply
Содержание FR-D700 Series
Страница 11: ...VII MEMO ...
Страница 23: ...12 MEMO ...
Страница 57: ...46 MEMO ...
Страница 262: ...258 MEMO ...
Страница 276: ...272 MEMO ...
Страница 283: ...279 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 287: ...283 MEMO ...
Страница 289: ......