Monitor display and monitor output signal
(3) Operation panel I/O terminal monitor
(Pr. 52)
When
Pr. 52
= "55", the I/O terminal status can be monitored on the operation panel.
The I/O terminal monitor is displayed on the third monitor.
The LED is on when the terminal is on, and the LED is on when the terminal is off. The center line of LED is always on.
On the I/O terminal monitor (
Pr. 52
= "55"), the upper LEDs denote the input terminal status and the lower the output
terminal status.
(4) Cumulative power monitor and clear
(Pr. 170, Pr. 891)
On the cumulative power monitor (
Pr. 52
= "25"), the output power monitor value is added up and is updated in 1h
increments.
The operation panel, parameter unit (FR-PU04/FR-PU07) and communication (RS-485 communication) display
increments and display ranges are as indicated below.
The monitor data digit can be shifted to the right by the number of
Pr. 891
settings.
For example, if the cumulative power value is 1278.56kWh when
Pr. 891
= "2", the operation panel display or parameter
unit (FR-PU04/FR-PU07) display is 12.78 (display in 100kWh increments) and the communication data is 12.
If the maximum value is exceeded at
Pr. 891
= "0 to 4", the power is clamped at the maximum value, indicating that a digit
shift is necessary. If the maximum value is exceeded at
Pr. 891
= "9999", the power returns to 0 and is recounted.
If the maximum value is exceeded at
Pr. 891
= "9999", the power returns to 0 and is recounted.
Writing "0" in
Pr. 170
clears the cumulative power monitor.
Operation Panel
Parameter Unit
∗2
Communication
Range
Unit
Range
Unit
Range
Unit
Pr. 170
= 10
Pr. 170
= 9999
0 to 99.99kWh
0.01kWh
0 to 999.99kWh
0.01kWh
0 to 9999kWh
0 to 65535kWh
(initial value)
1kWh/
0.01kWh
100.0 to 999.9kWh
0.1kWh
1000.0 to 9999.9kWh
0.1kWh
1000 to 9999kWh
1kWh
10000 to 99999kWh
1kWh
∗1
Power is measured in the range 0 to 9999.99kWh, and displayed in 4 digits.
When the monitor value exceeds "99.99", a carry occurs, e.g. "100.0", so the value is displayed in 0.1kWh increments.
∗2
Power is measured in the range 0 to 99999.99kWh, and displayed in 5 digits.
When the monitor value exceeds "999.99", a carry occurs, e.g. "1000.0", so the value is displayed in 0.1kWh increments.
∗3
In monitoring with communication, cumulative power is displayed in 1kWh increments. And cumulative power 2 is displayed in 0.01kWh. (
for communication)
REMARKS
If "0" is written to
Pr. 170
and
Pr. 170
is read again, "9999" or "10" is displayed.
RM
RL
RH
Free
STR
Free
Free
Free
Free
Free
Free
Free
Free
RUN
Free
Free Free
Free
Free
ABC
Free
Free
STF
Free
Center line is always on
Input terminal
- Display example -
When signals STF, RH and
RUN are ON
Output terminal
Hz
A
V
Содержание FR-D700 Series
Страница 11: ...VII MEMO ...
Страница 23: ...12 MEMO ...
Страница 57: ...46 MEMO ...
Страница 262: ...258 MEMO ...
Страница 276: ...272 MEMO ...
Страница 283: ...279 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 287: ...283 MEMO ...
Страница 289: ......