183
Communication operation and setting
4.19.5 Mitsubishi inverter protocol (computer link communication)
(1) Communication
The communication specifications are given below.
(2) Communication procedure
∗1
If a data error is detected and a retry must be made, execute retry operation with the user program. The inverter comes to trip if the number of consecutive
retries exceeds the parameter setting.
∗2
On receipt of a data error occurrence, the inverter returns retry data 3) to the computer again. The inverter comes to trip if the number of consecutive data
errors reaches or exceeds the parameter setting.
You can perform parameter setting, monitor, etc. from the PU connector of the inverter using the Mitsubishi inverter
protocol (computer link communication).
Item
Description
Related
Parameter
Communication protocol
Mitsubishi protocol (computer link)
Pr. 549
Conforming standard
EIA-485 (RS-485)
—
Number of connectable devices
1:N (maximum 32 units), setting is 0 to 31 stations
Pr. 117
Communication
speed
PU connector
Selected from among 4800/9600/19200 and 38400bps
Pr. 118
Control procedure
Asynchronous
—
Communication method
Half-duplex
—
Communication
Character system
ASCII (7 bits or 8 bits can be selected)
Pr. 119
Start bit
1bit
—
Stop bit length
1 bit or 2 bits can be selected
Pr. 119
Parity check
Check (even, odd) or no check can be selected
Pr. 120
Error check
Sum code check
—
Terminator
CR/LF (presence/absence selectable)
Pr. 124
Waiting time setting
Selectable between presence and absence
Pr. 123
Data communication between the computer and
inverter is made in the following procedure.
1) Request data is sent from the computer to
the inverter. (The inverter will not send data
unless requested.)
2) After waiting for the waiting time
3) The inverter sends return data to the
computer in response to the computer
request.
4) After waiting for the inverter data processing
time
5) Answer from the computer in response to
reply data 3) of the inverter is transmitted.
(Even if 5) is not sent, subsequent
communication is made properly.)
When data is read
When data is written
1)
5)
4)
3)
2)
*1
*2
Computer
(Data flow)
Inverter
Computer
(Data flow)
Inverter
Time
Содержание FR-D700 Series
Страница 11: ...VII MEMO ...
Страница 23: ...12 MEMO ...
Страница 57: ...46 MEMO ...
Страница 262: ...258 MEMO ...
Страница 276: ...272 MEMO ...
Страница 283: ...279 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 287: ...283 MEMO ...
Страница 289: ......