![MICRO-EPSILON C-Box/2A Скачать руководство пользователя страница 79](http://html.mh-extra.com/html/micro-epsilon/c-box-2a/c-box-2a_operating-instructions-manual_1785309079.webp)
Page 79
Appendix | ASCII Communication with Sensor
C-Box/2A
A 2.3.6.11 Data Selection
ANALOGOUT1 SENSOR1VALUE|SENSOR1INTENSITY|SENSOR1SHUTTER|SENSOR1REFLECTIVITY|SEN
SOR2VALUE|SENSOR2INTENSITY|SENSOR2SHUTTER|SENSOR2REFLECTIVITY|C-BOXVALUE|FIXED
[Wert]
Selection of the signal to be output via the analog output1.
For FIXED, the voltage / current value is indicated with four decimal places.
ANALOGOUT2 SENSOR1VALUE|SENSOR1INTENSITY|SENSOR1SHUTTER|SENSOR1REFLECTIVITY|SEN
SOR2VALUE|SENSOR2INTENSITY|SENSOR2SHUTTER|SENSOR2REFLECTIVITY|C-BOXVALUE|FIXED
[Wert]
Selection of the signal to be output via the analog output2.
For FIXED, the voltage / current value is indicated with four decimal places.
Default = SENSOR1VALUE
A 2.3.6.12 Output Range
ANALOGRANGE1 NONE|0-5V|0-10V|-5-5V|-10-10V|4-20mA
- NONE: No analog output (inactive)
- 0 - 5 V: The analog output1 outputs a voltage of 0 to 5 Volt.
- 0 - 10 V: The analog output1 outputs a voltage of 0 to 10 Volt.
- -5 - 5 V: The analog output1 outputs a voltage of -5 to 5 Volt.
- -10 - 10 V: The analog output1 outputs a voltage of -10 to 10 Volt.
- 4 - 20 mA: The analog output1 outputs a current of 4 to 20 milliamperes.
ANALOGRANGE2 NONE|0-5V|0-10V|-5-5V|-10-10V|4-20mA
- NONE: No analog output (inactive)
- 0 - 5 V: The analog output2 outputs a voltage of 0 to 5 Volt.
- 0 - 10 V: The analog output2 outputs a voltage of 0 to 10 Volt.
- -5 - 5 V: The analog output2 outputs a voltage of -5 to 5 Volt.
- -10 - 10 V: The analog output2 outputs a voltage of -10 to 10 Volt.
- 4 - 20 mA: The analog output2 outputs a current of 4 to 20 milliamperes.
Default = 0-10V