Service functions and error messages
Page 144
Product Manual „Servo drives ARS 2320, ARS 2340, ARS 2320W, ARS 2360W“
Version 8.0
Error message Meaning of the error message Measures
Main
index
Sub
index
4
PROFIBUS:
Range overflow
Mathematical error during the conversion of
physical units. The value range of the data and
of the physical units do not match (fieldbus
display units).
Contact the Technical Support.
25
0
Invalid device type
Please send the servo drive to our sales partner.
1
Device type not supported
2
HW revision not supported
Check the firmware version.
If necessary, request an update from the
Technical Support.
3
Device function restricted
Please send the servo drive to our sales partner.
26
0
No user parameter set
Load the default parameter set.
If the error continues to occur, contact the
Technical Support.
1
Checksum error
2
Flash:
Error during write-operation
Please send the servo drive to our sales partner
3
Flash:
Error during erase-operation
4
Flash: Error in internal flash
Re-load the firmware.
If the error continues to occur, contact the
Technical Support
5
No calibration data
6
Missing user position data sets Simply perform save & reset.
Load the default parameter set.
If the error continues to occur, contact the
Technical Support.
7
Faulty data tables (CAM)
Load the default parameter set and commission
the servo drive.
If necessary, reload parameter set.
If the error continues, contact the Technical
Support.