9 LTOS7 Management and Monitoring
9.2.2.3 Hardware subtree
mbgLtNgSysPsStatus
If a LANTIME has a redundant power supply (RPS) unit, it is important to check the status of both
RPS modules regularly. This PowerSupplyStatus OID can be found in the System Hardware subtree. The
following states are available:
Status
Description
——————————————————————————————————————————————-
0:
notAvailable:
The queried power supply unit is not recognized by a system. Check to see
if it is damaged, and replace it if necessary.
1:
down:
The power supply unit of interest is not in service. Check to see if it is damaged,
and replace it if necessary.
2:
up:
The queried power supply module is in operation.
It is recommended to check this OID every 60 s.
9.2.2.4 Misc subtree
mbgLtNgEthPortLinkState
In the mbgLtNgMisc subtree one can find an EthPortLinkState OID which identifies the status of each
physical Ethernet port of a LANTIME. Available values:
Status
Description
———————————————————————————————————————————————–
0:
notAvailable:
The queried port is down, check the link LED. If faulty,
replace the network card.
1:
up:
The port of interest is in normal operation.
It is recommended to check this OID every 60 s.