94
Sheeter SVC 525C
Set-up, commissioning
Making the stationary mains connection
7.3.5
Connecting additional protective equipotential bonding
The RFI filters of the frequency converters used generate a system-condi-
tioned grounding leakage current.
Since this can be greater than 10 mA, according to EN 60204-1 Clause
8.2.8 an additional protective equipotential bonding conductor is neces-
sary.
This should have a cross-section of 10 mm
2
.
Procedure:
1) Insert the protective equipotential bonding conductor into the main con-
trol cabinet through the cable grommet (1).
2) Connect the protective equipotential bonding conductor to the PE con-
nection terminal strip (2).
The protective equipotential bonding conductor is connected.
CAUTION!
Discharge currents greater than 10 mA.
Non-observance could result in property damage.
•
Connect the protective equipotential bonding conductor to the PE
terminals.
•
Cross-section 10 mm
2
(Cu).
1
PE connection terminal strip
2
Cable grommet
Illustration 44: Connection of protective equipotential bonding conductor
2
1