8.0 Using the ME-RC Remote
© 2012 Magnum Energy, Inc.
34
8.3 ME-AGS-N Operation/Monitoring using the ME-RC
This section covers the AGS menus in the ME-RC remote that determine how
to control and operate the generator. The section also includes menus that are
used to monitor starting and running conditions for the AGS and the generator.
• Enable
Select this option to have the AGS monitor temperature (
04
Start Temp F
) and/or the inverters battery voltage (
05 Start Volts
) to
determine when to automatically start the generator.
• Test
Select this option to test the generator. This option starts the
generator, runs it for approximately 30-60 seconds, and then stops the
generator. Use this setting for testing generator wiring and operation.
After a successful start/stop sequence test, this selection returns to
Off
.
• Enable w/QT
Select this option to have the AGS monitor tempera-
ture (
04 Start Temp F
) and/or the inverters battery voltage (
05 Start
Volts
) to determine when to automatically start the generator with the
Quiet Time parameters enabled.
WARNING:
Never allow the generator to start/run in an enclosed
garage or any other type of enclosed structure without proper ven-
tilation. Carbon monoxide, an odorless, colorless, deadly gas may
accumulate and cause serious injury or death.
AGS: 02 AGS Status Menu
This menu allows you to view the AGSs current status. There are 13 dif-
ferent status messages to identify the AGSs current state, but only one is
displayed at any one time (refer to the AGS menu map Figure 8-2).
Available statuses are (refer to Tables 11-1 thru 11-3 for detailed descrip-
tions of each):
AC In
Manual Run
No Comm
Fault Temp
Fault Test
Fault VDC
Lockout
8.3.2 Monitoring the AGS using the ME-RC
The following menus are helpful for the proper operation and monitoring
of your AGS/generator system. Press the AGS button, and then rotate and
press the SELECT knob to access the following menus:
8.3.1 Controlling the AGS using the ME-RC
Press the AGS button, and then rotate and press the SELECT knob to access
the following menus:
AGS: 01 AGS Control Menu
This menu is used to enable the AGS (selecting
Enable
or
Enable
w/QT
). A
Test
setting is also available to ensure the start/stop wiring from
the generator to the ME-AGS-N is correct. The available settings are:
• Off
This option disables the AGSs generator start/stop functions. It
also turns the generator off if it is running from an autostart command.
When
Off
is selected, the generator will not start automatically. This is
the default setting. If you have an AGS fault, select
Off
to clear the fault.
Info:
If DC power is lost to the remote or to the system, this menu
resets to the default
Off
position for safety.
Off
Quiet Time
Ready
Start Temp
Start Test
Start VDC