9.0 Using the ME-ARC Remote
© 2012 Magnum Energy, Inc.
42
Example:
Using a 12-volt battery as an example, a typical SOC (State of
Charge) battery chart will show that 12.2 VDC is considered 50% SOC. This
voltage is a battery at rest, meaning it has no load connected and has been
at rest for a minimum of 30 min. While this voltage is accurate under these
at rest conditions, this same voltage with a load applied means the battery is
well above 50% SOC, and should be set much lower. The larger the battery
bank the less the voltage will be affected by a load applied to the battery
bank. A typical start voltage setting would be between 11.0 VDC - 11.5 VDC
for a 12-volt system.
• Set Start Volts Delay
This setting determines how long the
Start
Gen Volts
parameter must be continuously maintained before the gen-
erator autostarts. This ensures the generator does not nuisance start.
By setting a delay, momentary surge loads will not start the generator
when the battery voltage dips due to the heavy load applied to the
battery.
Default setting:
Set Start Volts Delay = 120 Seconds
Range:
0 - 127 Seconds, 1 - 127 Minutes
Where should I set Start Volts?
When setting the VDC start voltage, it
must be high enough to not over-discharge the battery, but also low enough
to keep from nuisance starting the generator. Typically, start volts is set
based on what is determined to be approximately 50% of the battery ca-
pacity. Since this is an inverter/battery system, and the battery is normally
loaded, the VDC used to determine 50% battery capacity should be set lower
than what is shown on typical battery voltage SOC charts (approximately
11-11.5 in a 12-volt system), which show the battery at rest (not loaded).
Info:
The DC voltage the AGS uses to determine when to autostart is
displayed in the
AGS: 08 AGS TECH
menu under the
AGS VDC
meter.
Where should I set Start Volts Delay?
Determine what loads will be
running when the generator needs to start. The larger the load the shorter
the delay time setting. When a large load is applied to the battery bank the
battery voltage drops quickly, so the delay time should be short to ensure
the batteries are not over-discharged. If you are unsure what loads might
be running or where to set the start delay, error on setting a shorter time
such as the default of 2 minutes (to protect batteries from over-discharge).
SETUP: 04A Gen Run VDC Menu
This menu starts/stops the generator based on the battery voltage as shown
on the METER buttons
03B DC Volts-AGS
menu. This menu provides the op-
tion to start the generator when the battery voltage gets low, and to stop the
generator once the battery reaches a higher voltage level, or has been fully
charged and goes into the Float Charge stage. Using voltage to automatically
start and stop the generator is a common method because it is considered
the simplest and easiest to understand. The
04A Gen Run VDC
menu also
has a delay setting to minimize nuisance starts/stops and the short cycle run
times of the generator.
• Set Start Gen Volts
This setting will start the generator when the
battery voltage (on Terminals #3 & #4) decreases to or below this set-
ting continuously for the duration of the
Set Start Volts Delay
setting.
Default setting:
Set Start Gen Volts = 11.5 VDC (12v), 23.0 VDC
(24v), 46.0 VDC (48v)
Range:
OFF, 9.0-16.0 VDC (12v), 18.0-32.0 VDC (24v), 36.0-64.0 VDC
(48v)