© 2012 Magnum Energy, Inc.
64
10.0 Using the ME-RTR Router
where to set the
Stop Gen Volts
setting, it must be lower than the inverters
Absorb Voltage
setting (determined by the
SETUP: 03B Battery Type
menu).
Otherwise, the charger will enter Absorption Charge mode which is re-
quired to maintain the batteries at a constant voltage level and the bat-
tery voltage will not reach the
Stop Gen Volts
setting, which will cause the
generator to run until it is out of fuel or until it reaches the
SETUP: 04F Max
Gen Run Time
setting.
Therefore, after reading this some will think that they should just set the
Stop Gen Volts
setting slightly lower than the absorption level to ensure
the charger always reaches the
Stop Gen Volts
setting before it goes into
the Absorption Charge mode. However, temperature changes can affect the
absorb voltage setting
¹
and may require you to readjust the
Stop Gen Volts
setting seasonally. If you are in a normally cold climate (<32°F), the actual
absorb charge voltage will increase. So, the
Stop Gen Volts
setting should be
set well above the absorb voltage setting (~.5V above for 12-volt systems).
If you are normally in a hot climate (>95°F), the actual absorb charge volt-
age will decrease. In that case, the
Stop Gen Volts
setting should be set well
below the absorb voltage setting (~.5V below for 12-volt systems).
A simpler way to charge the batteries to 80-85% and to automatically allow
a temperature-compensated charge to the batteries (no seasonal adjust-
ment required) is accomplished using the settings below:
Set the
Stop Gen Volts
setting to
Float
Set the
Absorb Volts
setting (
SETUP: 03B Battery Type
) to the voltage
level at which you want the generator to turn off (normally
~ 14.5 volts
for
ooded batteries in a 12-volt system)
Set the
Absorb Done Time
setting (
SETUP: 03E Absorb Done Time
) to
0.1 hours
(lowest setting)
Using these settings, when the batteries reach a low voltage level the gen-
erator turns on (per the
Start Gen Volts
setting) and charges the battery to
the temperature-compensated
Absorb Voltage
setting. After reaching the
absorption voltage level, the inverter/charger goes into Absorption Charge
mode and is there for only 6 minutes (0.1 hours) before it goes to Float
Charge mode. Once the inverter/charger enters Float Charge mode, the AGS
will autostop the generator.
Info:
Battery life will be reduced if the batteries are only charged to
80-85% regularly. It is highly recommended to charge the batteries
to 100% as often as possible (~ once a week, or every other dis-
charge cycle) in order to avoid sulfation of the battery plates. Using
the
SETUP: 03E Absorb Done Time
menu, the absorption charge time
can easily be changed to a longer duration to increase the batteries
state of charge.
• Set Stop Volts Delay
This setting determines the amount of time
the generator will run after the
Set Stop Gen Volts
setting has been
satis
ed.
Default setting:
Set Stop Volts Delay = 60 Seconds
Range:
OFF, 1 - 120 Seconds, 3 - 127 Minutes
Note
¹
:
When the inverters Battery Temperature Sensor (BTS) is connected,
the actual absorb charge voltage will increase or decrease to ensure correct
charging as the battery temperature changes.