9.0 Using the ME-ARC Remote
Table 9-2, Software Differences Between ME-ARC Revisions (Cont.)
AGS Menu
(Button: Menu)
AGS Menu
Selections/Adjustments
Inverter
Level
ME-AGS-N
Required
ME-ARC
Required
SETUP: 04 AGS Setup (Cont.)
04B Gen Run
Time
OFF, ON, Start/Stop =
12AM-12PM
Level 1
Rev 5.0
Rev 2.0
04C Gen Run
Amps
*
OFF, Start/Stop = 5-60
amps AC
Level 4
Rev 5.0
Rev 2.0
Start/Stop Delay = 0-127
sec., 1-127 min.
04D Gen Run
SOC
**
OFF, Start = 20-90%
Level 1
Rev 5.0
Rev 2.0
Stop = 21-100%
04E Gen Run
Temp
Start = OFF, Ext Input,
65-95F
Level 1
Rev 5.0
Rev 2.0
Gen Run Temp Time =
0.5-6.0 Hours
Gen Run Temp Time =
0.5-25.5 Hours
Level 1
Rev 5.0
Rev 2.4
04F Max Gen
Run Time
0.0-25.5 Hours
Level 1
Rev 5.0 &
5.1
Rev 2.0
OFF-25.5 Hours
Level 1
Rev 5.2
Rev 2.3
04G Quiet
Time
OFF, ON, Start = 12AM-
12PM
Level 1
Rev 5.0
Rev 2.0
Stop = 12AM-12PM
Quiet Time Topoff = OFF,
30, 60, 90, 120 min.
04H Gen
Exercise
OFF, Days = 1-255
Level 1
Rev 5.0
Rev 2.0
Run Hour = 12AM-12PM
Run Time = 0.0-25.5 Hrs
04I Gen
Warm-up
Time
0-127 sec., 1-127 min.
Level 1
Rev 5.0
Rev 2.0
04J Gen
Cooldown
Time
0-127 sec., 1-127 min.
Level 1
Rev 5.0
Rev 2.0
TECH:
01 Tempera-
tures
AGS: Read Only
Level 1
Rev 5.0
Rev 2.0
02 Revisions
AGS: Read Only
Level 1
Rev 5.0
Rev 2.0
Active AGS Fault
Fault LED = off, Fault sta-
tus = view using METER:
03A AGS Status menu
Level 1
Rev 5.0
Rev 2.0
Fault LED = blinking, Fault
status = alternates with
inverter/charger status
Level 1
Rev 5.0
Rev 2.3
*
Only works with MS-PAE or MS-PE inverters.
**
The Gen Start/Stop SOC feature requires the ME-BMK (Battery Monitor).