8.0 Using the ME-RC Remote
Info:
When the
RV
mode is used and the AGS system feature is
required, the user will need to re-enable the AGS system each time
the generator is manually turned on or off.
Info:
If the AGS is automatically disabled when using
RV
mode, the
AGS status displays
Lockout
.
• AGS Rev
Displays the software revision of the connected AGS.
Info:
The AGS accessory may display a
0.0
revision for several
reasons. Either the AGS is not installed, there is no communication
because of a bad or miswired network cable, the AGS is not pow-
ered, or the AGS is bad.
• AGS Mode
This setting allows you to con
gure the AGS to comply
with RVIA standards
¹
. When the AGS is set to
RV
, the AGS is auto-
matically disabled any time the generator is manually turned on or off.
Select
Other
if your system is for a RV, or your requirements do not
need the AGS to be disabled should the generator be manually started/
stopped.
Default setting:
AGS Mode = RV
Settings:
RV, Other
AGS: 08 AGS TECH Menu
This menu displays meter data on the operating condition of the generator
and AGS, and has an AGS mode setting.
• Gen Run
Displays the number of hours the generator has been cur-
rently running from an autostart condition. This menu does not deter-
mine run time when the generator has been manually started.
• AGS VDC
Displays the battery voltage currently connected to the AGS
(on Terminals #3 and #4). This voltage is used to power the AGS and is
the voltage reading the
05 Start Volts
setting is monitoring to determine
when to start.
• Temp
Displays the current temperature reading of the temperature
sensor and is the temperature the
04 Start Temp F
setting is monitoring
to determine when to start. If the temperature sensor is not installed,
the display will either show a very high temperature value (122C/252F),
or
TS open
displays depending on your remote revision.
Info:
This menu is important when determining if the AGS is working
correctly, or for troubleshooting an AGS installation.
Info:
For any fault mode displayed in the status menu, please refer
to Section 12.0 ME-AGS-N Remote Troubleshooting in this manual.
Note:
AGS menus
03-07
were covered in Section 8.1.
Note
¹
- RV manufacturers use the NFPA 1192 Standard on Recreational
Vehicles for installing an AGS system. This standard has a requirement that
states when the generator is manually turned on or off, the AGS system
must also be turned off. Selecting the RV setting satis
es this requirement
by automatically disabling the AGS system when it senses that the generator
has been manually turned on or off. In installations where the requirement
to automatically disable the AGS system is not needed, the Other setting
can be chosen. When the AGS is in the Other mode, manually turning the
generator off or on will not automatically disable the AGS system.