2.0 Installation
© 2012 Magnum Energy, Inc.
12
Figure 2-10, Generator Run Sense Options
DC Fuse
(5A max)
AGS Terminal Block Ports:
1 2 3 4 5 6 7 8
On Generator
120VAC Outlet
120VAC IN
12VDC OUT
TRANSFORMER
120 VAC Coil Relay
On Generator
NC
COM
NEU
HOT
NO
120VAC Outlet
Inside Generator
Generator
Battery
AGS Terminal Block Ports:
1 2 3 4 5 6 7 8
DC Fuse
(5A max)
Generator
Battery
Inside Generator
Generator
Running
Lamp
OR
Generator
Hour
Meter
0
1
2
3
DC Fuse
(5A max)
AGS Terminal Block Ports:
1 2 3 4 5 6 7 8
Alternative Option 3
Use an external 120 VAC coiled relay to bring the
generators battery voltage to the AGS gen run sense terminal (AGS terminal
block Terminal #2) only while the generator is running. The generators
battery voltage must be 10 to 40 VDC.
Alternative Option 2
Use a 120 VAC to 12 VDC step-down transformer
(normally used to charge power equipment batteries) and plug it into the
generators 120 VAC output. The step-down transformer provides 12 VDC
output only while the generator is running.
Alternative Option 1
Tap into the positive side of the generators hour
meter or running lamp; ensure the voltage is 10 to 40 VDC only while the
generator is running.