10.0 Using the ME-RTR Router
10.4 Enabling the ME-AGS-N using the ME-RTR
Before the AGS can begin operating and monitoring for an autostart condition
(using the active AGS settings in your ME-RTR router), it must be enabled.
From the AGS Home screen (to access, refer to info in Section 10.2.1.1):
1. Press the CTRL button on the ME-RTR router, and then rotate the SELECT
knob to the
03 Gen Control
menu.
2. Press the SELECT knob. The
Set Gen Control
screen displays with the
current gen control setting and an arrow to the right.
10.5 Starting and Stopping the Generator using the
ME-RTR
Using the available settings from your ME-RTR router, the generator can be
manually and automatically started/stopped.
To autostart/autostop the generator:
In order for the generator to autostart/autostop, one or more of the follow-
ing autostart/autostop conditions must be pre-set (see Section 10.1):
The AGS is now ready to automatically start/stop the generator once an
autostart condition is satis
ed.
Note:
If power is lost to your remote, the AGS control setting will return to the
default
OFF
setting. Once power is restored, you must enable the AGS again.
Note:
Despite enabling the AGS, you must check the AGSs current status
(either by viewing the AGS Home screen or under the
METER: 03A AGS Status
menu) and ensure the status displays as
Ready
.
3. Turn the SELECT knob to the
AUTO
setting.
4. Press the SELECT knob to select this setting. The selection arrow appears
to the right of the screen
TECH: 03 Firmware Versions
This menu displays the software/
rmware version of all the network devices
connected directly to the network ports of the connected inverter. (P1acc-
P6acc). If an AGS is connected, the screen alternates the AGS display with
the revision of the connected AGS.
Info:
The AGS accessory may display a
0.0
revision for several
reasons. Either the AGS is not installed, there is no communica-
tion because of a bad or miswired network cable, or the AGS is not
powered or is bad.
Autostart Conditions
04A Gen Run VDC (pp. 62-64)
04B Gen Run Time (p. 65)
04C Gen Run Amps (pp. 65-66)
04D Gen Run SOC (pp. 66-67)
04E Gen Run Temp (pp. 67-68)
04G Quiet Time (pp. 69-71)
04H Gen Run Exercise (pp. 71-72)
Autostop Conditions
04A Gen Run VDC (pp. 62-64)
04B Gen Run Time (p. 65)
04C Gen Run Amps (pp. 65-66)
04D Gen Run SOC (pp. 66-67)
04E Gen Run Temp (pp. 67-68)
04F Max Gen Run Time (p. 69)
04G Quiet Time (pp. 69-71)
04H Gen Run Exercise (pp. 71-72)