© 2012 Magnum Energy, Inc.
9.0 Using the ME-ARC Remote
OFF:
The
OFF
selection turns the generator off if it is running from either a
manual on command or an autostart command. When
OFF
is selected, the
AGS is prevented from starting the generator automatically (default).
Info:
When
OFF
is selected, the AGS turns off immediately without
any cooldown time (if set).
CTRL: 03 Gen Control
This menu is used to manually turn the connected generator on and off, or
to select the
AUTO
feature which enables the active generator autostart and
autostop settings to control the connected generator. Available options are:
9.3 ME-AGS-N Operation/Monitoring using the ME-ARC
This section provides the menus under the ME-ARCs CTRL, METER, and TECH
buttons that determine how to control and operate the generator. The section
also includes menus that are used to help monitor the AGS and the genera-
tors starting and running conditions.
9.3.1 Controlling the AGS using the ME-ARC
The AGS uses the
CTRL: 03 Gen Control
menu to activate the generator either
manually or automatically. Press the CTRL button on the ME-ARC remote and
rotate the SELECT knob to the
03 Gen Control
menu.
Note:
If the generator attempted to start but did not run, continue to wait,
the AGS will attempt to start the generator 3 more times.
If your AGS/generator system started (may attempt an autostart 4 times),
ran, and the STATUS LED came on and stayed on (not blinking), then the
wiring from the AGS to the generator is correct. You are now ready to enable
the AGS by setting the
03 Gen Control
setting in your remote to
AUTO
(see
Section 9.3.1).
Info:
The AGS attempts to start the generator 4 times. If after 4
attempts the generator fails to start, the STATUS LED turns red
indicating a fault.
If a generator fault displays or the AGS modules STATUS LED shows a fault
condition (solid red LED indication), refer to Section 12.0 for assistance.
9.2.1.2 Starting the Generator from the Remote
To con
rm that the generator will turn on and run from the remote,
rst ensure
the AGS status is
Off
or
Ready
(see Section 9.2.1.1). Then:
1. Press the CTRL button, and rotate the SELECT knob to the
03 Gen Con-
trol
menu.
2. Press the SELECT knob, and then rotate it to the
ON
setting.
3. Press the SELECT knob to activate the generator test.
Once the generator starts, it should run until you change the
03 Gen Control
menu to
OFF
(before turning off). After two minutes, view the STATUS
LED and ensure it turns solid green (a solid green STATUS LED means the
generator has started successfully and is providing the gen run sense signal
to the AGS module).
Info:
If DC power is lost to the remote or to the inverter system,
this menu resets to the default
OFF
position for safety.
Info:
If the generator is manually started from the generator control
panel or a generator remote panel, selecting
OFF
may not shut down
the generator.