© 2012 Magnum Energy, Inc.
90
12.0 ME-AGS-N Remote Troubleshooting
12.2 Resolving Operational Statuses
The following operational statuses can display on your remote control, and
some may indicate an abnormal condition. This section provides additional
information and assistance to resolve these statuses (if needed).
• No Comm
This is a normal status if there is no AGS installed. If an
AGS is installed, use the information below to determine the remedy.
Remedy:
If an AGS is installed, then follow these steps:
1. Ensure the green READY indicator on the AGS module is on (blink-
ing or solid) to indicate that the AGS module is getting power
(see Figure 5-1).
2. Ensure the communications cable is connected from the Network
port on the Magnum inverter to the NETWORK port on the ME-AGS-N
(see Figures 2-5 and 2-6).
3. Ensure you have the correct communications cable
(see Figure 2-4).
• AC In
This is a normal status when the input to the inverter/charger is
connected to an AC source such as utility/grid power, or to an alternate
generator that may not be controlled by the AGS.
Remedy:
The
AC In
status prevents the AGS from autostarting. To
enable the AGS to autostart the generator, remove any AC power
connected to the input of the inverter/charger.
• Lockout
This is a normal status (ME-RC only) whenever the AGS is
con
gured to comply with RVIA requirements (for use in an RV). This
status displays whenever the generator is started or stopped for any
condition outside the control of the AGS. To clear or disable the
Lockout
status, refer to the remedies below.
Remedy:
To clear a
Lockout
status: Ensure the generator is off. On
the ME-RC, go to the
AGS: 01 AGS Control
menu (the current set-
ting should be
AGS = Off
) and press the SELECT knob to re-enter
the
Off
selection. Once you re-select the
Off
setting, the
Lockout
status will clear (now should read
Off
). You must re-enable the
AGS for autostart operation by changing the AGS control from
AGS
= Off
to
AGS = Enable,
or
AGS= Enable w/QT
(under the
AGS: 01
AGS Control
menu).
Remedy:
To disable the
Lockout
feature: If the AGS in not used in an
RV installation (or you do not need to comply with RVIA requirements),
you can disable the
Lockout
feature. Under the
AGS: 08 AGS TECH
menu, access the
AGS Mode
setting and change it from
RV
to
Other
(
AGS Mode = Other
). For more information on this setting, refer to the
AGS mode under the
AGS: 08 AGS TECH
menu on page 35.
12.3 ME-AGS-N Faults using your Remote
For the eight faults that follow, refer to the Remedy immediately following
the list.
• Fault Temp
The generator failed to autostart and run per the
04 Start
Temp F
menus (ME-RC) or the
04E Gen Run Temp
menus (ME-ARC and
ME-RTR) start parameters.