12.0 ME-AGS-N Remote Troubleshooting
• Fault Test
The generator failed to autostart and run after
Test
is
selected under the
AGS: 01 AGS Control
menu in the ME-RC, or the red
TEST button is pressed on the AGS module (using any remote).
Note:
The ME-ARC and ME-RTR do not provide a test selection, in-
stead they can be set to manually turn the generator on and off, which
can be used to test the generator wiring to the AGS.
• Fault VDC
The generator failed to autostart and run per the
05 Start
Volts
(ME-RC) or the
04A Gen Run VDC
(ME-ARC & ME-RTR) menus
start parameters.
• Fault Amp
The generator failed to autostart and run per the
04C Gen
Run Amps
(ME-ARC & ME-RTR only) menus start parameters.
• Fault Exercise
The generator failed to autostart and run per the
04H
Gen Exercise
(ME-ARC & ME-RTR only) menus start parameters.
• Fault SOC
The generator failed to autostart and run per the
04D Gen
Run SOC
(ME-ARC & ME-RTR only) menus start parameters.
• Fault Time
The generator failed to autostart and run per the
04B Gen
Run Time
(ME-ARC & ME-RTR only) menus start parameters.
• Fault Topoff
The generator failed to autostart and run per the
04G
Quiet Time Topoff
(ME-ARC and ME-RTR only) start parameters.
Remedy:
One of the above fault messages may display on the remote
control when:
A. The AGS attempts to start the generator four times, but the gen
failed to start and run per the speci
c autostart parameters; or,
B. The generator started, but did not provide the correct gen run
sense signal to the AGS module. For either scenario, refer to Section
6.2 to troubleshoot why the generator does not start or run.
• Fault MaxRn
The generator has turned off because the gen run time
after autostarting has exceeded the
SETUP: 04F Max Gen Run
Time
setting (ME-ARC and ME-RTR only).
Info:
The
Max Gen Run Time
menu uses the
SETUP: 04B Gen Run
Time
display to determine the generators run time. Cooldown and
warm-up times are not included in the
Gen Run Time
display.
Remedy:
Con
rm that all the autostop parameters that are active or
enabled can be satis
ed before the
SETUP: 04F Max Gen Run Time
setting is reached.
If using the
SETUP: 04A Gen Run VDC
menus parameters:
with a battery voltage setting to autostop, ensure the auto-
stop voltage is less than the temperature-compensated absorb
charge voltage.
with the
Float
setting to autostop, ensure the time that the
charger is in the Bulk Charge and Absorb Charge
¹
stages is shorter
than the
04F Max Gen Run Time
setting.
Refer to your remotes
SETUP: 04A Gen Run VDC
section for ad-
ditional information on this setting.
Note
¹
:
Several conditions determine the length of time that
the charger is in the Absorb Charge stage. Ensure the SETUP:
03E Absorb Done (Time, Amps, or SOC) setting determines
when the Absorb Charge stage is complete and enters the Float
stage is taken into account when setting the 04F Max Gen
Run Time setting.