96
Parameter
Name
Description
Setting Range
1 : General-Purpose Motor (Standard Motor)
2 : Drive Dedicated Motor
(Constant Torque Range 1 : 10)
3 : Vector Motor (Constant Torque Range 1 : 100)
4 : Derated Torque PM Motor
5 : Constant Torque PM Motor
(Constant Torque Range 1 : 500)
Sets 0 (disabled) when using one drive to run
more than one motor. Install an overload relay
between the drive and each motor.
P1-01
Motor Overload
Protection Time
Sets the time for the drive to shut down on motor
overload.
Default: 1.0 minute
Min.: 0.1 minutes
Max.: 5.0 minutes
P1-02
Retain
P1-03
Motor Overheat
Fault Operation
Selection (MT
Input)
Selects the drive operation when the MT input
signal reaches the level of motor overheat fault.
0
∶
Ramp to Stop
1
∶
Coast to Stop
2
∶
Fast Stop (Follows the fast stop time set in
C1-08)
Default: 1
Range: 0 to 3
P2: Momentary Power Loss
P2-00
Momentary Power
Loss Operation
Selection
0 : Disabled (Default)
1 : Recover if CPU Has Power
2 : KEB function if CPU Has Power
3 : Ramp to Stop with KEB Deceleration
Default: 0
Range: 0, 1, 2, 3
P2-01
Minimum
Baseblock (bb)
Time
Sets the minimum baseblock time when power is
restored right after a momentary power loss. This
determines the time the drive waits for the
residual voltage in the motor to dissipate.
Increase this value if overcurrent or overvoltage
occurs at the beginning of Speed Search and DC
Braking.
Default: Determined by
o2-03, A1-06
Min.: 0.1 s
Max.: 5.0 s
P2-02
Sets the detection
time of low voltage
(UV1) during
operation
In-service low voltage (UV1) detection time
Default: 0 ms
Min.: 0 ms
Max.: 1000 ms
P2-03
Uv (Undervoltage )
Detection Level
Sets the voltage level of undervoltage detection or
KEB function activation.
Default: Determined by
d1-00, o2-03
Min.: 150V
Max.: 210V <3>
Содержание EVO 8000 Series
Страница 1: ......
Страница 3: ...7 4 MODBUS Data List 142 APPENDIX UL DESCRIPTION 156...
Страница 15: ...12 2 2 Nameplate Model Number Applicable motor rating Input power supply Output power supply...
Страница 48: ...45 4 3 2 1 Multi Function Digital Input Wiring Diagram...
Страница 49: ...46 4 3 2 2 Pulse input wiring diagram...
Страница 55: ...52 F1 F4 F5 F6 Figure 4 4 4 DIP Switch RS 485 Termination Resistor OFF ON...
Страница 169: ...166 22F 392 Ruey Kung Road Neihu Taipei City 114 Taiwan...