68
Parameter
Name
Description
Setting Range
pause function) and b5-29/b5-30 (PID wake
function) are valid.
6: PID control is valid (frequency c PID
output, D control for feedback value method
2)
b5-01 <4>
Proportional Gain
Setting (P)
Sets the P gain for PID input.
Default
∶
1.00
Min.: 0.00
Max.: 25.00
b5-02 <4>
Integral Time
Setting (I)
Deviation appears between PID target value and
feedback value when using only proportional
control. To reduce the deviation, set integral time
(I).
Default
∶
1.0 s
Min.: 0.0 s
Max.: 360.0 s
b5-03 <4>
Integral Time (I)
Limit Setting
Sets the maximum output from the I (integral)
control as a percentage of the maximum
frequency (d1-02)
Default
∶
100.0%
Min.: 0.0%
Max.: 100.0%
b5-04 <4> Derivative Time (D) Sets derivative time for D control.
Default
∶
0.00 s
Min.: 0.00 s
Max.: 10.00 s
b5-05 <4> PID Output Limit
Sets the maximum output from PID control as a
percentage of the maximum frequency.
Default
∶
100.0%
Min.: 0.0%
Max.: 100.0%
b5-06 <4>
PID Bias Voltage
Adjustment
Sets the PID bias voltage adjustment as a
percentage of the maximum frequency to add to
the PID control output.
Default
∶
0.0%
Min.: -100.0%
Max.: 100.0%
b5-07 <4>
PID Primary Delay
Time
Sets the delay time for the PID output filter.
Default
∶
0.00 s
Min.: 0.00 s
Max.: 7.00 s
b5-08
PID Output
Selection
0
∶
Normal PID Output
1
∶
Reverse PID Output
Reverses the +/- sign of the PID output
Default
∶
0
Min.: 0
Max.: 1
b5-09 PID Output Gain
Sets a PID output gain
Default
∶
1.00
Min.: 0.00
Max.: 25.00
b5-10
PID Output Reverse
Selection
Determines whether or not a negative PID output
reverses the drive rotating direction.
0 : Reverse Disabled
1 : Reverse Enabled
Default
∶
0
Min.: 0
Max.: 1
b5-11
PID Feedback Low
/High Detection
Selection
0
∶
Multi-Function Output Only
1
∶
Feedback Low /High Alarm
The drive continues operation when an alarm
is displayed)
Default
∶
0
Min.: 0
Max.: 7
Содержание EVO 8000 Series
Страница 1: ......
Страница 3: ...7 4 MODBUS Data List 142 APPENDIX UL DESCRIPTION 156...
Страница 15: ...12 2 2 Nameplate Model Number Applicable motor rating Input power supply Output power supply...
Страница 48: ...45 4 3 2 1 Multi Function Digital Input Wiring Diagram...
Страница 49: ...46 4 3 2 2 Pulse input wiring diagram...
Страница 55: ...52 F1 F4 F5 F6 Figure 4 4 4 DIP Switch RS 485 Termination Resistor OFF ON...