116
Parameter
Name
Description
Setting Range
U3-09: 12345MWh
U3-09
<7>
5 digits of kWh
(cumulative power)
Display the output power of the inverter on the
monitor.
Displayed separately according to the high and low
bits (display example) The monitor at
12345678.9kWh is displayed as: U3-08: 678.9kWh
U3-09: 12345MWh
0.1kWh
U3-10 Peak Hold Current
Displays the peak current value during operation
0.01A
U3-11
Peak Hold Output
Frequency
Displays the output frequency when the peak
current displayed in U3-10 occurred.
0.01Hz
U3-12
Motor Overload
Estimate (oL1)
Displays the value of the motor overload detection
accumulator. An oL1 will be triggered when
reaching 100%.
1%
U3-13
Frequency Command
Source Selection
Displays the source for the frequency command as
XY-nn.
X: Command Used
1: Command 1
2: Command 2
Y-nn: Frequency Command Source
0-01: Keypad
1-01: Analog input (Terminal AI 1)
1-02: Analog input (Terminal AI 2)
2-02 to 2-16: Multi-step speed command
2-17: Jog frequency command
3-01: PID frequency command
4-01: Terminal UP/ DOWN
5-01: Modbus communication
6-01: Pulse train command
-
U3-14
Run Command Source
Selection
Displays the source for the frequency command as
XY-nn.
XY-nn=00-00: Local
X: Command Used
1: Command 1
2: Command 2
Y-nn: Command Source
0-00: Keypad
0-01: Control Circuit Terminal (Sequence Control
Input)
0-02: Modbus communication
-
U3-15 Frequency hold value Display frequency hold value
Hz
U3-16 Retain
U3-17 Drive Overload
Displays the value of the drive overload detection
1%
Содержание EVO 8000 Series
Страница 1: ......
Страница 3: ...7 4 MODBUS Data List 142 APPENDIX UL DESCRIPTION 156...
Страница 15: ...12 2 2 Nameplate Model Number Applicable motor rating Input power supply Output power supply...
Страница 48: ...45 4 3 2 1 Multi Function Digital Input Wiring Diagram...
Страница 49: ...46 4 3 2 2 Pulse input wiring diagram...
Страница 55: ...52 F1 F4 F5 F6 Figure 4 4 4 DIP Switch RS 485 Termination Resistor OFF ON...
Страница 169: ...166 22F 392 Ruey Kung Road Neihu Taipei City 114 Taiwan...