67
Parameter
Name
Description
Setting Range
<9>
time
voltage to the set V/F curve voltage during speed
search
Min.: 0.3 s
Max.: 5.0 s
b3-03 Retain
b3-04
<9>
Speed search
deceleration time
Set the deceleration time in the speed finding
action (the time until the highest output
frequency decelerates to the lowest output
frequency.
Default
∶
2.0 s
Min.: 0.1 s
Max.: 10.0 s
b3-05
<9>
V/F in speed search
In order to reduce the output current in the speed
search, the voltage calculated by the V/F curve is
multiplied by the set value of b3-05. By adjusting
this setting, the output current in the speed
search can be suppressed.
Default
∶
100%
Min.: 10%
Max.: 100%
b3-06
ASR proportional (P)
gain during speed
search
Default
∶
0.6
Min.: 0.01
Max.: 30.00
b3-07
ASR integral (I) gain
during speed search
Default
∶
2.80
Min.: 0.01
Max.: 30.00
b3-08
Speed search
feedback filter
Set the speed of the motor to feedback the
low-pass filter time during speed search
Default
∶
0.1 s
Min.: 0 s
Max.: 1.000 s
b4: Timer Function
b4-00
Timer Function
On-Delay Time
Sets the on-delay and off-delay time to switch
on/off the timer output.
Default
∶
0.1 s
Min.: 0.1 s
Max.: 3000.0 s
b4-01
Timer Function
Off-Delay Time
Default
∶
0.1 s
Min.: 0.0 s
Max.: 3000.0 s
b5: PID Control
b5-00 PID Control Setting
0
∶
PID Control Disabled
1
∶
PID Control Enabled (D Control for Deviation
Signal U4-01)
2
∶
PID Control Enabled (D Control for Feedback
Signal U4-05)
3
∶
PID Control Enabled (Frequency Command
+
PID Output from D Controlled Deviation)
4
∶
PID Control Enabled (Frequency Command
+
PID Output from D Controlled Feedback)
5: PID control is invalid, but b5-14/b5-15 (PID
Default
∶
0
Min.: 0
Max.: 6
Содержание EVO 8000 Series
Страница 1: ......
Страница 3: ...7 4 MODBUS Data List 142 APPENDIX UL DESCRIPTION 156...
Страница 15: ...12 2 2 Nameplate Model Number Applicable motor rating Input power supply Output power supply...
Страница 48: ...45 4 3 2 1 Multi Function Digital Input Wiring Diagram...
Страница 49: ...46 4 3 2 2 Pulse input wiring diagram...
Страница 55: ...52 F1 F4 F5 F6 Figure 4 4 4 DIP Switch RS 485 Termination Resistor OFF ON...
Страница 169: ...166 22F 392 Ruey Kung Road Neihu Taipei City 114 Taiwan...