7.4 MODBUS Data List
The MODBUS data list is as follows. The types of data include command data, monitoring data, and
broadcast transmission data.
Instruction DATA (can be read and written)
Site
Definition
2400H
Retain
2401H
Operational order
BIT 0
Stop/Run (0: Stop, 1: Run)
BIT 1
Forward/reverse (0: forward, 1: reverse)
BIT 2
External fault EF0 0: No function 1: External
fault
BIT 3
Fault reset 0: No function 1: Fault reset
BIT 4
Retain
BIT 5
Retain
BIT 6
Retain
BIT 7
Retain
BIT 8
Multi-function terminal 1 (0:Off,1: ON)
BIT 9
Multi-function terminal 2 (0:Off,1: ON)
BIT 10
Multi-function terminal 3 (0:Off 1: ON)
BIT 11
Multi-function terminal 4 (0:Off 1: ON)
BIT 12
Multi-function terminal 5 (0:Off 1: ON)
BIT 13
Multi-function terminal 6 (0:Off 1: ON)
BIT 14
Multi-function terminal 7 (0:Off 1: ON)
BIT 15
Multi-function terminal 8 (0:Off 1: ON)
2402H Frequency command (unit: 0.01Hz)
2403H
Torque
command
(-16384
~
16384
corresponds to -200% ~ 200% motor rated
torque)
Monitor DATA (read only)
Site
Definition
2420H
Retain
2421H
Operational state
BIT 0
1: In operation
Содержание EVO 8000 Series
Страница 1: ......
Страница 3: ...7 4 MODBUS Data List 142 APPENDIX UL DESCRIPTION 156...
Страница 15: ...12 2 2 Nameplate Model Number Applicable motor rating Input power supply Output power supply...
Страница 48: ...45 4 3 2 1 Multi Function Digital Input Wiring Diagram...
Страница 49: ...46 4 3 2 2 Pulse input wiring diagram...
Страница 55: ...52 F1 F4 F5 F6 Figure 4 4 4 DIP Switch RS 485 Termination Resistor OFF ON...
Страница 169: ...166 22F 392 Ruey Kung Road Neihu Taipei City 114 Taiwan...