51
F5-F6
Figure 4.4.3 DIP Switch AM
Table 4.4.3 DIP Switch AM Setting (Terminal AM)
Setting
Description
V
Voltage output (0 to 10 V)
I
Current output (4 to 20 mA or 0 to 20 mA) (default)
Table 4.4.4 Parameter 4-04
No
Parameter Name
Description
Setting
Range
Default
E4-04
Terminal AM Signal Level
Selection
Selects the signal level for terminal
AM
0 : 0 to 10 V
1 : 0 to 20 mA
2 : 4 to 20 mA
0, 1, 2
2
4.4.4 RS-485 Communication Termination ON / OFF Switch
The default of termination resistor for RS-485 communication is OFF. Switch it to ON when the drive
is the last in a series of slave drives. Set this termination resistor on DIP switch RS485 illustrated in
Figure 4.4.4.