43
4.3.1.2 Output Terminals
Table 4.3.1.2 Control Circuit Output Terminals
Terminal Type
Terminal
Code
Terminal Name
Terminal Description
Multi-Function
Relay Output
R1A
Relay 1 normal open
Relay output
DC 30 V, 3 A
AC 250 V, 5 A
R1B
Relay 1 normal closed
R1C
Relay 1 common
R2A
Relay 2 normal open
R2C
Relay 2 normal closed
Multi-Function
Photocoupler
Output
D1
Photocoupler Output terminal 1 (zero speed)
Photocoupler Output
48 V, 2 to 50 mA
D2
Photocoupler Output terminal 2 (speed agree)
DC
Photocoupler Output terminal
Multi-Function
Analog Output
FM
Programmable analog output terminal (output
frequency)
Voltage Output
0 to 10V, -10 to +10V
AM
Multi-function analog output terminal (output
current )
Voltage or current output
(Selectable) 0 or 4 to
20mA, 0 to 10V
AC
Analog common terminal
Multi-Function
Pulse Train
Output
MP
Multi-function
pulse
train
output
(output
frequency)
32KHz Max
PC
Pulse train common terminal
<1> Do not assign frequent switching functions such as ON/OFF to terminals R1 and R2, which may
shorten the relay terminal life.
Содержание EVO 8000 Series
Страница 1: ......
Страница 3: ...7 4 MODBUS Data List 142 APPENDIX UL DESCRIPTION 156...
Страница 15: ...12 2 2 Nameplate Model Number Applicable motor rating Input power supply Output power supply...
Страница 48: ...45 4 3 2 1 Multi Function Digital Input Wiring Diagram...
Страница 49: ...46 4 3 2 2 Pulse input wiring diagram...
Страница 55: ...52 F1 F4 F5 F6 Figure 4 4 4 DIP Switch RS 485 Termination Resistor OFF ON...
Страница 169: ...166 22F 392 Ruey Kung Road Neihu Taipei City 114 Taiwan...