70
Parameter
Name
Description
Setting Range
<7>
limit
output of the PID control being lower than the
specified value. The d1-02 (the highest output
frequency) is set to 100% in %.
The d1-02 (the highest output frequency) is set to
100% in %.
Min.: -100.0%
Max.: 100.0%
b5-21
<7>
PID input limit value
When the input value of the PID control is large,
the output of the PID control will also become
larger. If the input value of the PID control needs
to be limited, it can be limited by the parameter
setting.
Default
∶
1000.0%
Min.: 0.0%
Max.: 1000.0%
b5-22
PID Feedback High
Detection Level
Sets the level for PID feedback high detection as a
percentage of the maximum output frequency.
PID feedback high will be detected when the
feedback exceeds the level set in b5-22 for longer
than the time set in b5-23.
Default
∶
100%
Min.: 0%
Max.: 100%
b5-23
PID Feedback High
Detection Time
Sets the time for PID feedback high detection. PID
feedback high will be detected when the feedback
exceeds the level set in b5-22 for longer than the
time set in b5-23.
Default
∶
1.0 s
Min.: 0.0 s
Max.: 25.5 s
b5-24
PID Target Display
Value
Sets a value to display to U4-00 and U4-03 when
the drive runs at the maximum output frequency
Determined by b5-19
Min.: 1
Max.: 60000
b5-25
PID Target Display
Digits
Sets the number of decimal places to display.
0
∶
No Decimal Places
1
∶
1 Decimal Place
2
∶
2 Decimal Places
3
∶
3 Decimal Places
Determined by b5-19
Min.: 0
Max.: 3
b5-26
<7>
Frequency
command display
selection during PID
0 : Reflects the frequency command after PID
compensation
1 : Reflects the frequency command before PID
compensation
Default: 0
Min.: 0
Max.: 1
b5-27
<7>
Inverted selection
of PID output 2
0 : When the output of PID is negative => Reverse
is prohibited
1 : When the output of the PID is negative =>
Allow reverse
Default: 1
Min.: 0
Max.: 1
b5-28
PID Disconnection
Output Frequency
When a PID feedback disconnection alarm occurs,
the drive will run at the frequency set to b5-28,
and return to PID control when disconnection
alarm is reset.
Default: 30.0 Hz
Min.:0.0Hz
Max.: <5>
b5-29
<9>
PID wake-up
function action
Set the action value for PID wakeup
Default: 0.0 Hz
Min.:0.0Hz
Содержание EVO 8000 Series
Страница 1: ......
Страница 3: ...7 4 MODBUS Data List 142 APPENDIX UL DESCRIPTION 156...
Страница 15: ...12 2 2 Nameplate Model Number Applicable motor rating Input power supply Output power supply...
Страница 48: ...45 4 3 2 1 Multi Function Digital Input Wiring Diagram...
Страница 49: ...46 4 3 2 2 Pulse input wiring diagram...
Страница 55: ...52 F1 F4 F5 F6 Figure 4 4 4 DIP Switch RS 485 Termination Resistor OFF ON...
Страница 169: ...166 22F 392 Ruey Kung Road Neihu Taipei City 114 Taiwan...