71
Parameter
Name
Description
Setting Range
value
Max.: <5>
b5-30
<9>
PID wake-up action
delay time
Delay the PID action value time setting
Default: 0.0 s
Min.:0.0 s
Max.: 25.5 s
b5-31 PID limit selection
When b5-00 = 3, 4, 6 (PID and frequency
command superimposed),
Adjust the baseline value of b5-05
0 : 100% of b5-05 corresponds to the highest
output frequency
1 : 100% of b5-05 corresponds to the frequency
command
Default: 0
Min.:0
Max.: 1
b6: Dwell Function
b6-00
Dwell Frequency at
Start
Sets the frequency to b6-00 used to be held for
the time set in b6-01 during acceleration.
Default
∶
0.0 Hz
Min.: 0.0 Hz
Max.: <5>
b6-01
Dwell Time at
Start
Default
∶
0.0 s
Min.: 0.0 s
Max.: 10.0 s
b6-02
Dwell Frequency at
Stop
Sets the frequency to b6-02 used to be held for
the time set in b6-03 during deceleration.
Default
∶
0.0Hz
Min.: 0.0 Hz
Max.: <5>
b6-03
Dwell Time at
Stop
Default
∶
0.0 s
Min.: 0.0 s
Max.: 10.0 s
b7 : Drop Control Function
b7-00 Droop control gain
When the torque command is 100%, the
deceleration value is set in % (maximum output
frequency = 100%).
When set to 0.0%, Droop control is invalid.
Default
∶
0
%
Min.: 0 %
Max.: 100 %
b7-01
Droop controlled
delay time
Adjusts the responsiveness of Droop control.
Please lower the setting when the response is
slow.
Default
∶
0.05 s
Min.: 0.03 s
Max.: 2.00 s
b7-02
Droop control limit
selection
0 : Droop control limit is invalid
1 : Droop control limit is valid
Default
∶
1
Min.: 0
Max.: 1
b8: Retain
b9 :
Position control / zero servo function <7>
b9-00
Position control /
zero servo gain
In the FOCPG mode, set the responsiveness of the
zero servo function.
Default
∶
0.5 %
Min.: 0 %
Содержание EVO 8000 Series
Страница 1: ......
Страница 3: ...7 4 MODBUS Data List 142 APPENDIX UL DESCRIPTION 156...
Страница 15: ...12 2 2 Nameplate Model Number Applicable motor rating Input power supply Output power supply...
Страница 48: ...45 4 3 2 1 Multi Function Digital Input Wiring Diagram...
Страница 49: ...46 4 3 2 2 Pulse input wiring diagram...
Страница 55: ...52 F1 F4 F5 F6 Figure 4 4 4 DIP Switch RS 485 Termination Resistor OFF ON...
Страница 169: ...166 22F 392 Ruey Kung Road Neihu Taipei City 114 Taiwan...