98
Parameter
Name
Description
Setting Range
continues when the output current drops 15%
below the value set in P3-01.
P3-01
Stall Prevention
Level during
Acceleration
Sets the output current level to activate the Stall
Prevention function during acceleration.
Default: 150%
Min.: 0%
Max.: 180%
P3-02
Stall Prevention
Limit during
Acceleration
Sets the lower limit of Stall Prevention in the
constant power range as a percentage of the drive
rated output current.
Default: 50%
Min.: 0 %
Max.: 100 %
P3-03
Stall Prevention
during Deceleration
0 : Disabled
The drive decelerates according to the set
deceleration time
1 : Enabled (Without Braking Resistor)
Default: 1
Range: 0 to 3
P3-04
Stall Prevention
Level during
Deceleration
Sets the voltage level to activate the Stall
Prevention function during deceleration.
Default: 395V
Min.: 330V
Max.: 410V <3>
P3-05
Stall Prevention
during Run
0 : Disabled
1 : Enabled (Deceleration Time 1)
2 : Enabled (Deceleration Time 2)
Default: 1
Range: 0, 1, 2
P3-06
Stall Prevention
Level during Run
Sets the current level to activate the Stall
Prevention function during run.
Default: 150%
Min.: 30%
Max.: 180%
P3-07
OVP function switch
Set to 1 to turn on the OVP function: the main
circuit voltage is too high during operation to
automatically increase the output frequency.
Default: 0
Min.: 0
Max.: 1
P3-08
OVP action level
Set the OVP function action level. During the
running process, the main circuit voltage is higher
than this parameter and P7-07=1, the OVP
function starts to operate.
Default: 370 V
Min.: 150V
Max.: 400V <3>
P3-09
Deceleration stall
prevention to
change voltage level
Set the change voltage value of the deceleration
stall prevention action
Default: 3.0 V
Min.: 0 V
Max.: 10.0 V
P3-10
Acceleration/decele
ration gain during
OVP
Set the ratio of acceleration and deceleration time
during OVP. The higher the
acceleration/deceleration time, the faster.
Default: 1.00
Min.: 0.10
Max.: 10.00
P3-11
Stall Deceleration
Time during
Acceleration
Sets the deceleration time for a stall during
acceleration
Default: 0.0 s
Min.: 0.0 s
Max.: 6000 s
P3-12
OVP frequency
acceleration
component
Frequency acceleration component when setting
OVP action
Default: 0
Min.: 0
Max.: 10.000
P3-13
OVP frequency
Frequency deceleration component when setting
Default: 0
Содержание EVO 8000 Series
Страница 1: ......
Страница 3: ...7 4 MODBUS Data List 142 APPENDIX UL DESCRIPTION 156...
Страница 15: ...12 2 2 Nameplate Model Number Applicable motor rating Input power supply Output power supply...
Страница 48: ...45 4 3 2 1 Multi Function Digital Input Wiring Diagram...
Страница 49: ...46 4 3 2 2 Pulse input wiring diagram...
Страница 55: ...52 F1 F4 F5 F6 Figure 4 4 4 DIP Switch RS 485 Termination Resistor OFF ON...
Страница 169: ...166 22F 392 Ruey Kung Road Neihu Taipei City 114 Taiwan...