April 17, 2000
Man ual Versio n 1.0
5.5
NOTE!
A counterbalance pressure that is far too low or far too high during any shut height
adjustment may place excessive load on the shut height adjust motor and may even
stall the motor. This condition can also occur with non-automatic motorized slide
adjust systems. If the automatic slide adjust doesn’t see slide adjust movement within
two seconds of a command to move, it will stop its command to move and generate
the Fault message “Slide Did Not Move”.
IMPORTANT!
Automatic movement will be terminated if the ESTOP button, “JOG UP”
softkey, “JOG DN” softkey, or “CANCEL AUTO ADJUST” softkey is
pressed while the slide is moving automatically. Automatic movement will
pause if the slide adjust switch is turned off. It will resume when the slide
adjust switch is turned back on.
the slide adjust screen or when a stored job is recalled and the system is “ON”. Note that the “AUTO
ADJUST” key will only appear when the slide adjust switch is ON and the editing cursor is on the slide
adjust setpoint of a slide adjust system. An auto adjust sequence always approaches the slide setpoint
from above. For instance, if the current position is 10.000 and the slide setpoint is 12.000, the auto
adjust sequence might take the slide first to 12.015, then back to 12.004, and then “pulse” the slide the
last four thousandths into position. This is to ensure consistent setups by taking up gear lash from the
same direction every time.
Note that a slide setpoint of 00.000 (used to store a job that will not
overwrite the previous slide setpoint on recall), will prohibit automatic adjustment
. Automatic
movement is subject to the following conditions:
a) The slide adjust switch must be on.
b) The press must be stopped.
c) The press must be at the top of the stroke.
d) The hydraulic overload on the press, if present, must not be tripped.
e) The Link Master Control (LMC) relay must be engaged.
f) There must be no faults in the slide system and the counterbalance system, if present.
g) The auto adjust sequence for the slide will not start until the counterbalance system, if present, is
at least up to its pressure setpoint. If the
correct
pressure setpoint for the counterbalance has
been entered, this will ensure that the counterbalance has taken up any clearances in the slide
connection system to increase accuracy of shut height adjustment. When the slide adjust system
waits for the counterbalance system to finish adjusting to its pressure setpoint, the status
message of the slide adjust system will be “Waiting for Cntr-Bal”.
Содержание OmniLink 5000
Страница 5: ...April 17 2000 Manual Versio n 1 0 iv...
Страница 38: ...April 17 2000 Manual Versio n 1 0 4 14...
Страница 63: ...April 17 2000 Manual Versio n 1 0 B 2 Figure B 2 Typical Cushion Wiring Diagram...
Страница 64: ...April 17 2000 Manual Versio n 1 0 B 3 Figure B 3 Conceptual Dual Resolver Mounting...
Страница 65: ...April 17 2000 Manual Versio n 1 0 B 4 Figure B 4 Typical AMCI Dual Resolver Wiring Diagram...
Страница 66: ...April 17 2000 Manual Versio n 1 0 B 5 Figure B 5 Typical GEMCO Dual Resolver Wiring Diagram...
Страница 67: ...April 17 2000 Manual Versio n 1 0 B 6 Figure B 6 Conceptual Linear Transducer Mounting...
Страница 68: ...April 17 2000 Manual Versio n 1 0 B 7 Figure B 7 Typical GEMCO Linear Transducer Wiring...
Страница 69: ...April 17 2000 Manual Versio n 1 0 B 8 Figure B 8 Typical MTS Temposonics II Linear Transducer Wiring...
Страница 71: ...April 17 2000 Manual Versio n 1 0 B 10...
Страница 73: ...April 17 2000 Manual Versio n 1 0 C 2...