![Laversab 6600-NG Скачать руководство пользователя страница 67](http://html1.mh-extra.com/html/laversab/6600-ng/6600-ng_user-manual_3905006067.webp)
6600-NG User’s Manual
125-9110A
Page 67
SECTION 4 : PROFILES
Profiles are created in Microsoft Excel and loaded into the 6600-NG through the COM1 port on your PC
using the Hyperterminal program that is normally available on all PC’s.
4.1
WHAT IS A PROFILE
A profile is a set of up to 50 points that tell the 6600-NG what you would want it to do at each point.
Each point consists of 12 parameters: 1) Pt units, 2) Pt mode, 3) Pt target value, 4) Pt Rate target value, 5)
Ps1 units, 6) Ps1 mode, 7) Ps1 target value, 8) Ps1 Rate target value, 9) Ps2 units, 10) Ps2 mode, 11) Ps2
target value and 12) Ps2 Rate target value. These 12 parameters are defined by you in the Excel program.
A total of 10 such profiles can reside in the 6600-NG at any time. Each profile is identified by a number
between 1 to 10 and also a name which can have up to 12 characters. The profile number and the name
are also part of the profile that is created in Excel.
A typical profile named “Sample” is shown below as it would appear in Excel.
A
B
C
D
E
F
G
H
I
J
K
L
1
Profile
2 Sample
3
0
3
knots
Control
100.0
150.0
Feet
Control
0
6000
Dfin
Control
0.0000
4.000
4
knots
Control
200.0
150.0
Feet
Control
0
6000
Dfin
Control
0.1000
4.000
5
knots
Leak
200.0
150.0
Feet
Control
0
6000
Dfin
Control
0.1000
4.000
6
knots
Control
100.0
150.0
Feet
Control
1000
6000
Dfin
Control
0.2000
4.000
7
knots
Control
200.0
150.0
Feet
Control
5000
6000
Dfin
Control
0.3000
4.000
8
knots
Control
300.0
150.0
Feet
Control
10000
6000
Dfin
Control
0.4000
4.000
9
knots
Control
100.0
150.0
Feet
Control
18000
6000
Dfin
Control
0.5000
4.000
10
knots
Control
100.0
150.0
Feet
Leak
18000
6000
Dfin
Control
0.5000
4.000
11
knots
Control
100.0
150.0
Feet
Control
30000
6000
Dfin
Control
0.6000
4.000
12
knots
Control
100.0
150.0
Feet
Control
50000
6000
Dfin
Control
0.7000
4.000
13
knots
Control
20.0
150.0
Feet
Control
Ground
6000
Dfin
Control
0.0000
4.000
14
knots Measure
20.0
150.0
Feet
Measure
Ground
6000
Dfin
Measure
0.0000
4.000
15
END
Row 1 always says “Profile”. This indicates to the 6600-NG that a profile is to follow.
Row 2 left cell shows the name of the profile. This profile is named “Sample”. The name can have up to
12 alphanumeric characters. This name will be displayed on the Remote unit when this particular profile
is Executed (Run).
Row 2 middle cell shows the number of the profile. This profile has a number 3. This tells the 6600-NG
that this profile is to be loaded in as profile number 3. When profile 3 is Run on the 6600-NG, this
“Sample” profile will be executed. This number can be any number between 1 and 10. When this profile
is loaded into the 6600-NG it will overwrite the previous profile that was resident in the 6600-NG as
number 3.