BDS5
C
HAPTER
2 - I
NSTALLATION
2-19
In this manual, instructions
that you enter will be shown
in italics and surrounded by a
double line box. The response
from the BDS5 will be in plain
upper case letters.
2.7.1 Checking Discrete Inputs
You can check the state of all of the discrete inputs
with the print command. This process will be
demonstrated with the hardware travel limit switch,
LIMIT. If you are not using the LIMIT switch, you
can substitute another hardware switch, such as
CYCLE or HOME which are available on Connector
C2. In this case, substitute the words "CYCLE" or
"HOME" for "LIMIT" in the following discussion.
1.
Open the switch contacts.
2.
Verify that the contacts are open. If you are
using an Industrial Drives Input Module or an
industry standard OPTO-22 compatible input
module, there will be an LED on each input to
indicate its state. The LED will be off if the
contacts are open.
3.
Use your terminal to enter:
P LIMIT
4.
The BDS5 should respond with "0" indicating
that the contacts are open.
5.
Close the switch contacts.
6.
Verify that the contacts are closed. (LED should
be on.)
7.
Use your terminal to enter:
P LIMIT
8.
The BDS5 should respond with "1" indicating
that the contacts are closed.
Repeat this process for each discrete input that you are
using:
__I1
__I2
__I3
__I4
__I5
__I6
__I7
__I8
__I9
__I10
__I11
__I12
__I13
__I14
__I15
__I16
__CYCLE
__GATE
__HOME
__LIMIT
__MANUAL
__MOTION
__REMOTE**
** Note that if a fault condition exists, the state (on
or off) of REMOTE may not be available. In this
case, the value of REMOTE will print as -1.
2.7.2 Checking General Purpose
Outputs
You can check all of the general purpose outputs by
turning them on and then off. Be careful. The
procedure in this section will activate all of the general
purpose outputs. Be sure that activating an output will
not cause a hazard to personnel or damage to
equipment.
Commands in this section will
turn on all general purpose
outputs. Be certain that this
is not a safety hazard. Make
sure this will not damage
equipment.
1.
Turn on O1 by typing:
O1 ON
2.
Verify that the output is on. If you are using an
Industrial Drives Input Module, or an industry
standard OPTO-22 compatible input module,
there will be an LED on each output to indicate
its state. The LED will be on if the output is on.
3.
Turn off O1 by typing:
O1 OFF
WARNING
NOTE
Содержание BDS5
Страница 2: ......
Страница 3: ...BDS5 INSTALLATION AND SETUP MANUAL Old Number M93101 ISSUE 4 New Number MB5000H...
Страница 4: ......
Страница 8: ......
Страница 10: ......
Страница 18: ......
Страница 20: ......
Страница 62: ...CHAPTER 2 INSTALLATION BDS5 2 26...
Страница 73: ...BDS5 CHAPTER 4 MAINTENANCE...
Страница 74: ...CHAPTER 4 MAINTENANCE BDS5...
Страница 78: ...CHAPTER 4 MAINTENANCE BDS5 4 4...
Страница 86: ...APPENDIX A WARRANTY INFORMATION BDS5 A 2...
Страница 88: ...APPENDIX B DRAWINGS BDS5 B 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 116: ......
Страница 131: ...APPENDIX E ON LINE REFERENCE GUIDE BDS5 E 2...