Maintenance
If the equipment is used in smoke heat extraction systems
(SHE), it must be checked, serviced and, if necessary,
repaired at least once per year. This is also recommended for
purely ventilation systems.
Clean the equipment. Check the tightness of fixing and
locking screws. Test the devices by a trial run according
to the Chapter start up procedure and trial run. The gear
systems of the linear drives are maintenance-free.
Defective equipment must be repaired in our plant. Only
original spare parts are to be used. Check regularly that the
equipment is ready for service. To this purpose we
recommend a service contract with the manufacturer or
another authorized specialist. All standard batteries provided
with the SHE control panel require regular checks as part
of the maintenance programme and are to be replaced
after the specified service life (4 years). Observe the legal
requirements when disposing of hazardous materials - e.g.
batteries. Reset of the maintenance timer if activated.
The operating instructions of the connected components
must be strictly observed!
Out of order
In order to put the SHE system out of order, the control panel
must be disconnected from the mains and the battery fuse
has to be taken off. During the period out of operation the
activated service timer stops and stores the last forwarded
data. As soon as the central control system is once again
connected to the mains the service timer continues to run as
usual.