39
Technical Manual
Kingspan SHE Control Panel TRZ Plus
2A and TRZ Plus Comfort
12/24999513
Technical Data
Automatic alarm unit output
Voltage:
24 V nominal
Power:
max. 150 mA, 100 % ED
Terminal:
max. 1 mm², spring terminal
Cable monitoring function:
End resisted 10k or active end module
max. Pieces:
10
Emergency power:
yes
Buzzer/Signal lamp output or 27V output voltage source
Voltage:
27 V nominal
Power:
max. 100 mA, 100 % ED
Terminal:
max. 1 mm², spring terminal
Cable monitoring function:
no
max. Pieces:
1
Emergency power supply:
no
Fuse:
no
Mechanical properties
Dimensions:
see pages 25 - 26
Weight:
TRZ Plus 2A: approx. 8 kg with battery, approx. 3 kg without battery
TRZ Plus Comfort: approx. 8 kg with battery, approx. 3 kg without battery
Compact Control panel 2A, 2A/M: approx. 15 kg with battery,
approx. 10 kg without battery
Circuit connections and operation
Connections:
see technical documentation
Terminal connections:
see technical documentation
Suitable for SHE:
yes
Suitable for ventilation:
yes
Ventilation function in the event of mains failure:
no, ventilation blocked
Safety functions in the event of mains failure:
yes, automatic closure of the windows, ventilation blocked, while SHE
continues to be active: further functions via DIP-Switches
Maintenance
Battery replacement:
every 4 years and in the event of battery malfunction
Maintenance counter:
yes, adjustable via PC Service Port Software
Maintenance counter active:
when power is supplied to the system, battery-backed
Functions after countdown of maintenance counter: LED display flashes, deactivation/activation of the via service port
software
Adjustable functions
Parameterisation:
yes
Parameterisation by means of:
DIP-Switches, related software
Options:
maintenance counter, actuation limit, automatic ventilation,
Further functions dependent on the software and firmware versions.
Installation and ambient conditions
Rated temperature:
20 °C
Ambient temperature range:
-5 °C to +40 °C
Installation condition:
dry
Function retention:
Drives: 72 hours
Magnetic clamps: 1 ¼ hours
Suitable for external mounting:
no
IP protection system:
TRZ Plus: IP 30 in accordance with EN 60 529
Compact control panal 2A: IP 44 in accordance with EN 60 529
Compact control panal 2A/M: IP 20 in accordance with EN 60 529,
IP30 when mounted