Equipment Overview /
Function
• SHE control panel for opening and closing of smoke vents in case of
fire and ventilation.
• Control of 24V DC motors with their own load or limit with a total
power consumption of max. 2A.
• Function “daily ventilation”
• One SHE group and one ventilation group
• 24V power supply, emergency power batteries and charging unit,
parallel operation, 72 hours of functioning guaranteed in case of
power failure
• Line monitoring of alarm circuits (autom. detectors and SHE man.
call points)
• Line monitoring of the connected drives
• Optical malfunction alarm
• Separately fused power input 230V AC / 50 Hz
• Hinged door or cover, lockable
• Conforms to current state-of-the-art standards
• Processor controlled
• Versatile connection facilities
• Service port interface included
• TÜV type tested
• Tested according to EN 12101-10
Scope of Delivery
• 1 x SHE control panel
• 1 x rechargeable batteries
• 2 x velcro tapes for fastening the batteries (Compact Control panel
2A, 2A/M)
• 1 x set of operating instructions
TRZ Plus 2A
TRZ Plus 2A Comfort
Compact Control panel 2A
(Plastic housing)
Compact Control panel 2A/M
(M = Metal housing)
Compact control panel 2A and
Compact control panel 2A/M
For smoke heat extraction and daily
ventilation to control 24 V DC linear drives
and chain motors
Please keep these operating instructions for future reference and maintenance. Subject to technical modifications. Diagram is not binding.