33
Technical Manual
Kingspan SHE Control Panel TRZ Plus
2A and TRZ Plus Comfort
12/24999513
Assembly
TRZ Plus and TRZ Plus Comfort
Mount the control panel with suitable plugs and screws
through the mounting
holes on the backside of the control panel. No overhead
installation or
rotated by 180 ° mounting.
The integrated display has to be mounted exactly 1.40 m
high from the ground.
Note:
The Control panel is also available with a
UP-mounting kit.
Inserting the rechargeable batteries
(TRZ Plus and TRZ Plus Comfort)
1.
Remove battery cover
2.
The batteries of adjacent wiring diagram connected in
series and connect (connection diagram on. Battery
cover included)
3.
Install the battery cover
Attention:
Ensure the correct polarity on the
batteries!
Compact control panel 2A
Wall mounting :
1.
First remove the baseplate with control electronics.
2.
Fix the housing through mounting holes with suitable
plugs and screws to the wall.
3.
Encase the baseplate back.
Note:
The control system must be fitted in a dry area
at a place that is easily visible and accessible.
No overhead installation or rotated by 180 °
mounting.
The control system must not be hidden by wall
projections, doors or structures.
Assembly:
Once the housing has been fastened to the wall:
1. Insert ventilation plug on the underside of the housing
Note:
Operating the control system without the
ventilation plug can lead to malfunction and is not
permitted!
Take care that the ventilation plug
is not covered by the rechargeable batteries!
Attention:
Start up procedure of the control panel
only with installed plexiglass cover.
Note:
The Control panel is also available with a UP-
mounting kit.
TRZ Plus Comfort
SMOKE VENT
1,4 m
STOP
Ventilation
plug
Bottom part of
housing
+
-
-
+
Sicherungsübersicht
Fuse layout
Legende /
:
F1 Netzsicherung /
F2 Motorsicherung /
F3 Akkusicherung /
Key
mains fuse
motor fuse
battery fuse
Akustische Störmeldung
Malfunction message beep-code chart
Akkulageplan
Battery connection diagram
Beep Code, LED (gelb /
)
yellow
0 > ---------------- OK
1 > 1--------1-----
Netzausfall /
mains failure
2 > 1-1------------
Störung Akku /
battery malfunction
3 > 1-1-1--------- Störung RWA-Bedienstelle /
malf. SHE manual call point
4 > 1-1-1-1-------Störung autom. Melder /
malfunction detector
5 > 1-1-1-1-1-----
Störung Motorüberwachung /
malf. motor monitoring circui
t
-
+
-
+
Akkuverbindungskabel
Battery cable
Battery cover
TRZ Plus
Batteries