38
Technical Manual
Kingspan SHE Control Panel TRZ Plus
2A and TRZ Plus Comfort
12/24999513
Technical Data
The power supplies and electrical control equipment are to be operated exclusively with the components authorised by
the manufacturer.
Electrical properties
Power supply means
ELV:
class A
Primary energy :
mains
Secondary energy:
battery
maximum interruption time between energy sources: < 1 ms
Primary energy supply
Operating voltage supply:
230 V AC / 50 Hz, (±10 %), separately fused
System voltage:
27 V DC (nominal) (-30 % / +10 %)
Power consumption:
max. 75 W
Power consumption (Standby):
TRZ Plus 2A: < 5 W
TRZ Plus Comfort: < 5 W
TRZ Plus Compact: < 5 W
Monitoring:
yes, Software monitoring
Terminal:
screw terminals max. 2.5 mm²
Fuse:
F1 main: Print-fuse 1.25 A/T TE5 250 V
Secondary energy supply
Batteries:
2 x 12 V, 1.2 Ah, VdS
Battery type:
lead gel battery
Emergency power:
72 h
Stand-by current:
11,5mA according to EN 12101-10
Power output after 72 h in Emergency operation:
2A for 180 sec. according to EN 12101-10
maximum current output:
2A (switched off at the primary energy source)
Charging time:
24 h for emergency power
Terminal:
max 1.5 mm², 4.8 blade terminal with insulating bush 200 mm long
Monitoring:
yes, cyclical, total discharge prot.
Fuse:
F3 battery, FKS 5A
Output
Voltage:
Drives/Magnetic clamps: 27 V DC (nominal), (-25 % / +10 %)
power:
Pmax = 54W; Pmin = 0W
Ripple:
Drives/Magnetic clamps: <1 %
Power (nominal):
Drives: 2 amp 30 % ED
Magnetic clamps:
0.7 amp 100 % ED
Power (temporary):
2.6 amp (≤600 ms)
Opening / closing sequence:
reversal of voltage polarity
Pause time during change of polarity:
200 ms
Timing in accordance with prEN 12 101-9:
yes, alteration of direction of travel every 2 min
Automatic activation:
Open/Close direction: after 3 min* (at ventilation operation)
Open direction:
after 30 min (at SHE operation)
Cable monitoring function:
via third monitoring circuit in conjunction with monitoring diodes
Terminal:
max. 2.5 mm², screw terminal
Drives / Magnetic clamps:
in accordance with max. current draw of the drives / magnetic clamps
Fuse:
FKS 5A
Call point output
Voltage: 24 V nominal
Power: max. 60 mA, 100 % ED
Terminal: max. 1 mm², spring terminal
max. Pieces: 10
Emergency power: yes