36
Technical Manual
Kingspan SHE Control Panel TRZ Plus
2A and TRZ Plus Comfort
12/24999513
Service Port Software
It is possible to save the configuration as a file on the hard
drive or other location. To do this, select “File” > “Save
configuration“ from the menu. Other options are loading a
file or printing a report.
Once the configuration editing is finished, the connection
between “TRZ Plus <> PC” must be disconnected using the
“Off” button. After that the service Port Software can be
closed down and the connection cable disconnected.
2. Adjustment possibilities (configuration)
using the Service Port Software
2.1 Automatic ventilation
When this function is activated, a ventilation time in
minutes (max. 10 min.) can be adjusted manually.
After using the vent switch operation, the drive closes
according to the adjustment.
If vent switch operation is interrupted, this function is
deactivated and is not reactivated until opened again using
the vent switch button operation.
Note:
This function is deactivated when supplied.
2.2 Maximum opening using ventilation function
This function is used to set up stroke limitation by run time
(in seconds). In this connection to the maximum
stroke [mm] corresponds 300 seconds, the zero
Stroke [mm] (not extended) 0 seconds. A fixed interval
(eg 150 seconds) corresponds to a new fixed shorter
stroke. This function can only be used in the OPEN
direction and in combination with an active activation time.
Note:
This function is deactivated when supplied.
2.3 Pol change Time
The pole change time determines the pause time when
there is a change of polarity in the motor output current in
milliseconds (max. 5000 ms).