16
Technical Manual
Kingspan SHE Control Panel TRZ Plus
2A and TRZ Plus Comfort
12/24999513
Connecting Diagram Smoke Detector
All work to be carried out without mains supply (230 V AC) or any batteries connected. Route the connecting cables into the
control panel housing at the top. Connect all connecting cables according to the wiring diagram and make sure that they are
correctly connected. Incorrect connections or figure or colour mix-ups can lead to incorrect function of the control panel or of
the external components. The notes and installation directives in the technical documentation are always to be observed.
without smoke detector
one smoke detector
SSD 521
UTD 521
UTD 523
MSD 523
last smoke detector
several smoke detectors
SSD 521
UTD 521
UTD 523
MSD 523
one
smoke
detector
last smoke detector
last
smoke
detector
1. smoke
detector
18 19
10kΩ
18 19
+
+
1 2 3 4 5
6
1 2 3 4 5
6
10kΩ
1 2 3 4 5
6
+
1 2 3 4 5
6
10kΩ
18 19
1 2 3 4 5
6
+
+
18 19
+
+
18 19
+
10 kΩ Monitoring resistor
till Firmware V01.00.11: DIP-Switch 11 = OFF
from Firmware V01.00.12: DIP-Switch 11 = ON
active end modul / 2
till Firmware V01.00.11: DIP-Switch11 = ON
from Firmware V01.00.12 used as standard: DIP-Switch 11 = OFF
10kΩ