24
Technical Manual
Kingspan SHE Control Panel TRZ Plus
2A and TRZ Plus Comfort
12/24999513
Function of DIP-Switches
DIP-Switch 3 + 10:
Main Power supply error = ventilation open*
In case of main power error the motor line will be triggered into OPEN direction automatically after 30seconds and the
windows open (function according to VdS guideline 2895). The indication “Ventilation open” on the ventilation switch will
be disabled. The open position stays as long as the main power failure is detected, port will set voltage free after 3 minutes.
As soon as the main power is connected again, the motor line will be triggered for 3 Minutes in CLOSE direction to close the
windows.
DIP-Switch 4:
“Fire alarm system Open” and “Reset via 1 x fire alarm system closer contact”. Connection via the terminals
of the automatic detectors with additional UEB3-1K-EA module. Fire alarm system contact closed denotes SHE activation,
fire alarm system contact Open = SHE-Reset and also closure of the flaps/windows. A combination with an automatic
warning device is possible, but the Reset will have to be done solely via SHE-Reset button of the TRZ-Plus or when
configuration DIP-Switch 8 = ON additionally via Close-button of an SHE-manual calling point.
DIP-Switch 5:
Pre-alert
A malfunction signal will take place if an automatic detector releases, if more than one automatic detector releases SHE
release will take place
.
DIP-Switch 6:
Actuation limit
Time-dependent ventilation actuation limit. For adjustment see section on “Functional description/actuation limit“.
DIP-Switch 7:
Malfunction = SHE activation
In the event of a malfunction an SHE activation automatically takes place. A Reset is only possible after the malfunction has
been cleared.
DIP-Switch 8:
SHE Close (on the SHE operating station) = SHE-Reset
Enables a Reset at any Type RBH/3A SHE operating station.
DIP-Switch 9:
Ventilation in inching mode of operation (deadman button)
The drives only traverse to Open or Close while the button is pressed. This function can serve as a protective function for
“power-operated windows”, insofar as there is visual contact with the relevant windows from the button.
1 2 3 4 5 6 7 8 9
ON
10 11 12
1 2 3 4 5 6 7 8 9
ON
10 11 12
1 2 3 4 5 6 7 8 9
ON
10 11 12
1 2 3 4 5 6 7 8 9
ON
10 11 12
1 2 3 4 5 6 7 8 9
ON
10 11 12
1 2 3 4 5 6 7 8 9
ON
10 11 12
1 2 3 4 5 6 7 8 9
ON
10 11 12
1 2 3 4 5 6 7 8 9
ON
10 11 12
1 2 3 4 5 6 7 8 9
ON
10 11 12
1 2 3 4 5 6 7 8 9
ON
10 11 12
1 2 3 4 5 6 7 8 9
ON
10 11 12
1 2 3 4 5 6 7 8 9
ON
10 11 12
* from Firmware > V01.00.11