27
Technical Manual
Kingspan SHE Control Panel TRZ Plus
2A and TRZ Plus Comfort
12/24999513
Start Up Procedure and Trial Run
SHE manual call points
Press SHE Open switch briefly, the windows open completely.
The red LED display
- SHE activated - lights up.
The green display
OK
- Operation OK - lights up. The
continuous acoustical signal sounds (only by SHE man. call
point with buzzer and if the door contact switch is pressed).
Press switch Closed in the vent switch, no drive reaction.
Press Reset switch in the control panel, the windows close
completely. The red LED display
- SHE activated - goes
out. The green LED display
OK
- Operation OK- lights up. The
continuous acoustical signal stops.
Press SHE Open briefly, the windows open. During running,
press the Open and Closed switches in the vent switch at the
same time. No reaction at the windows, they must not stop.
Press the SHE-Reset switch in the control panel, the windows
close completely.
Test emergency power supply
Disconnect mains power supply, the green LED
OK
“operating OK” goes out (after max. 100 sec).
The yellow LED
- malfunction -flashes. In case of power
failure, the windows close immediately.
Press the “Open” switch of the vent switch, no window
reaction.
Press the switch SHE “Open”, the windows open.
The red LED
- SHE activation - is shining.
The green LED
OK
“operating OK” not lit up.
Press the switch “Closed” of the SHE manual call point, the
windows close completely.
The red LED
“SHE-activation” goes out. The yellow LED
“malfunction” flashes.
Re-connect mains voltage, the green LED
OK
“operating
OK” is shining after a moment. Reset the activation.
Test automatic detectors
Trigger the automatic detector (e.g. with test spray): the red
LED in the autom. detector is shining.
The red LED
“SHE activation” is shining.
The green LED
OK
“operating OK” is shining.
The windows open completely.
Press the switch “Closed” of the vent switch, no window
reaction. Get rid of the smoke in the detectors, otherwise
reactivation may occur.
Press the switch “SHE-Reset” in the control panel, the
windows close completely and the automatic detector is
Reset. The red detector LED goes out.
Test automatic ventilation control
(DIP-Switch 12 to ON)
Press Open switch in the vent switch, the windows open
completely. The windows close again automatically after 10
minutes.