9
Technical Manual
Kingspan SHE Control Panel TRZ Plus
2A and TRZ Plus Comfort
12/24999513
Cable Length Diagram
To determine the necessary cable cross-sections as a
function of the line length and the sum of the rated currents
of the drives.
m (simple line length)
Cable length diagram up to 2 amps for drives with a current draw < 2.5 A
0
1 2
a)
b)
c)
d)
e)
e)
6 mm²
d)
2 x 2,5 mm²
c)
4 mm²
b)
2,5 mm²
a)
1,5 mm²
50
100
150
200
250
300
350
400
450
500
Nominal drive current in amps
Cable Cross-Section Determination
Notes re-cable cross-section determination and cabling layout
Simplified formulae for cable cross-section determination (for drives up to 2.5
A nominal current draw)
Note:
Permissible current supply of the TRZ Plus has to be considered,
see technical data.
A = cable cross-section
I = sum of the rated drive current draws
*L = simple line length
73 = factor, made up from 2.5V max. permissible voltage drop and electrical conductivity of copper
A [mm²] =
*
(I [A] +
ggf. Aufschlag in %**
) x L [m]
73
A [mm²] =
*
(I [A] +
if so loading factor in %**
) x L [m]
73
A [mm²] =
I [A] x L* [m]
73
M
=
M
=
simple cabel
length(L*)
Notes re-selection of cables
For the motor supply cables of SHE drives 3 or 5 (duplicated
layout) individual cores are required.
Two cores (4 cores) are for the motor voltage, the 3rd or 5th
core respectively is required for monitoring the cabling.
The selection and layout of the cables is to be performed
according to (model) utility facilities guidelines (MLAR). Here
particular attention is to be paid to E30 or E90 functionality
retention!
3 x ... mm²
**
5 x ... mm²
3 x ... mm²
**
5 x ... mm²
M
=
yellow-green: cannot be used for
the calbing monitoring
brown
blue
Motor
Junction box
Motor voltage
Cabling monitoring
Cabling example
Examples of cable types and fittings that can be used
Cable system, consisting of load support system and cables
with appropriate fire protection tested wall plugs and
screws. Cable system in accordance with DIN 4102-12 and
BS 8519. Safety cable + layout system