26
Technical Manual
Kingspan SHE Control Panel TRZ Plus
2A and TRZ Plus Comfort
12/24999513
Start Up Procedure and Trial Run
Note:
The specifications for start up procedure
apply to the standard functions.
All DIP-Switches are OFF.
Note:
Before start up procedure the enclosed ferrite
core is arounded to the Battery connection cable
(see picture)
Without mains voltage and without battery
Check all parts mechanically and electrically for fully
tightened screw connections and damage, the terminals:
plug in connectors for motors and control elements as well
as, if available, automatic detectors and wind/rain detectors.
Do not plug in the battery fuse!
With mains voltage and battery
Switch on mains. Plug in battery fuse.
Visual display on the control board
Max. 100 secs. after connecting the battery, check:
green LED
OK
- Operation OK - lit up,
red LED
- SHE activation - not lit up,
yellow LED
- Malfunction - not lit up.
Note:
In case of malfunction, see chapter
“Troubleshooting” and “Fault finding”.
Troubleshooting
• Green LED
OK
not lit up: Mains and/or battery and
connection not OK.
• Red LED
lit up: Press SHE-Reset switch in the control
panel.
• Yellow LED
is flashing: - check corresponding fuses (see
also beep code chart page 57).
- cable breakage, check cable connections.
- check if end module is missing in last smoke detector.
Ferritkern
Battery lead
Vent switches
Press vent switch Open briefly, the drives open the windows
completely up to end position.
The display “ventilation Open” lights up. During running:
observe the windows exactly.
Attention:
Make sure the drives can move freely
at all times without obstruction. Pay attention to
potential collision, tension and crushing during this
movement, too. Check the connection cables of the
drives: they must not be strained by tension or
crushing.
Press vent switch Closed briefly, the drives close the window.
The display “Ventilation Open” goes out.
Press STOP during running, STOP = press both Open and
Closed switches at the same time, the drives stop. he display
“Ventilation Open” lights up.
Press vent switch Closed briefly once again, the drives close.
The display “Ventilation Open” goes out.
The drives close the window completely up to end position.
The display “Ventilation Open” goes out.
Attention:
Pay attention to potential collision,
tension and crushing during this movement, too.